HYDRONIC CASSETTE
64
2.A.4 MASTER-SLAVE CONFIGURATION
Master unit: close SW6 [DIP switch] before power on. Master will beep twice to the LCD wireless
handset or LCD wall pad confirming receipt of commands. Each master can command up to 31 slave
units.
Slave unit: open SW6 [DIP switch] before power on. Slave unit will beep once to the LCD wireless
handset or LCD wall pad confirming receipt of commands.
Important note: Data loggers are not applicable to Master-Slave System.
2.A.5 MASTER-SLAVE CONTROL
Above control PCB can receive data from both wireless LCD handset and wired wall pad. Once wall pad
is connected to the PCB, receiver from the unit will stop receiving signal from wireless LCD handset.
LCD handset can only provide signal to Wall Pad receiver. When wall pad is disconnected from the PCB
for 5 seconds, it will revert to wireless LCD handset reception automatically.
2.A.6 MASTER-SLAVE COMMUNICATION METHOD
There are two modes for Master-slave structure.
Global Control communication
Master will broadcast the settings to all slave units. During normal operation, slave units can receive
commands from its wireless handset and wall pad control panel. Upon reception of master global
commands, all slave unit settings will be replaced by the master settings.
Addressable communication
Master controller must be LCD wall pad. Slave unit parameters are set as usual. Upon receiving the
control commands from a master, the addressed slave unit settings will be replaced by the master
settings.
If master unit is equipped with wireless LCD handset only, it can only use Global-Control communication
method. If it is equipped with LCD wall pad, it can use both communication methods.
DIP1 used for master slave address setting.
DIP switch address setting: 1 for ON, 0 for OFF.
SW6 SW5 SW4 SW3 SW2 SW1 Unit
No. Remark
1 0 0 0 0 0 01 Master
0 0 0 0 0 0 01 Slave
- 0 0 0 0 1 02 Slave
- 0 0 0 1 0 03 Slave
- 0 0 0 1 1 04 Slave
- 0 0 1 0 0 05 Slave
- 0 0 1 0 1 06 Slave
- 0 0 1 1 0 07 Slave
- 0 0 1 1 1 08 Slave
- 0 1 0 0 0 09 Slave
- 0 1 0 0 1 10 Slave
- 0 1 0 1 0 11 Slave
- 0 1 0 1 1 12 Slave
- 0 1 1 0 0 13 Slave
- 0 1 1 0 1 14 Slave
- 0 1 1 1 0 15 Slave
- 0 1 1 1 1 16 Slave
- 1 0 0 0 0 17 Slave
Summary of Contents for PCG-06
Page 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Page 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Page 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Page 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Page 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Page 43: ...HYDRONIC CASSETTE 43 ...
Page 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Page 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Page 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Page 66: ...HYDRONIC CASSETTE 66 ...