HYDRONIC CASSETTE
53
DEHUMIDIFICATION MODE
1. MTV2, AUX1 and heater always off.
2. If Tr >= 25 ºC, MTV1 and AUX2 will be ON for 3 minutes, and OFF for 4 minutes.
3. If 16 ºC < =Tr < 25 ºC, MTV1 and AUX2 will be ON for 3 minutes, and OFF for 6 minutes.
4. If Tr <16 ºC, MTV1 and AUX2 will be turned off for 4 minutes.
At the end of the above dehumidification cycle, system will decide the next dehumidification control option.
Indoor fan will run at low speed throughout the dehumidification process.
AUTOMODE
1. If current running mode is auto cool mode, it will change over to auto heat mode upon satisfy all the
conditions below:
Ts-Tr
≧
1.0°C(or -4 ºC if economy contact is activated)
MTV1 has stop
≧
10 min.
2. If current running mode is auto heat mode, it will change over to auto cool mode upon satisfy all the
conditions below:
Tr-Ts
≧
1.0°C(or +4 ºC if economy contact is activated)
MTV2 has stop
≧
10 min.
Note: Auto cool or auto heat operation are the same as cool or heat mode respectively.
SLEEP MODE
a) Sleep mode can only be set in cool or heat modes only.
b) In cool mode, after sleep mode is set, the indoor fan will run at low speed and Ts will increase 2 ºC
during 2 hours.
c) In heat mode, after sleep mode is set, the indoor fan will run at set speed and Ts will decrease 2 ºC
during 2 hours.
d) Changing of operation mode will cancel sleep mode.
The cool mode sleep profile is:
The heat mode sleep profile is:
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts+0.5
Ts+1.0
Ts+2.0
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts-2.0
Ts-1.0
Ts-0.5
Summary of Contents for PCG-06
Page 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Page 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Page 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Page 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Page 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Page 43: ...HYDRONIC CASSETTE 43 ...
Page 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Page 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Page 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Page 66: ...HYDRONIC CASSETTE 66 ...