HYDRONIC CASSETTE
27
CONTORL BOX CONFIGURAITON
a) Plug-and-play control box with full functionality PCB (please refer to wiring diagram on
page 60)
The PCB is a universal type with multiple configurations selectable using dipswitches. Please
provide dip-switch setting according to below.
There are 2 DIP Switch sets on the PCB, one with 8 Dip-switches which named as DIP-Switch A
and one with 6 Dip-switches which named as DIP-Switch B
For master-slave connection setting, please refer to Appendix I.
DIP Switch A SW1-SW6 is used for master slave address setting.
DIP switch address setting: 1 for ON, 0 for OFF.
SW7 SW8 Model setting
0 0 Cool-Heat
0
1
Cool-Heat + booster heater
1 0 Cooling
only
1
1
Cool + primary heater
DIP Switch B is used for model configuration as follow:-
DIP switch setting: 1 for ON, 0 for OFF.
SW1 PR-O contact setting
0 Economy
contact
1 Window
contact
SW2 System
setting
0
2 pipes system
1
4 pipes system
SW3 Preheat
setting
0 28C
1 36C
SW4 MTV setting [applicable to 2 pipes system only]
0
Without motorized valve
1
With motorized valve
SW5 Reserved
SW6 RS485 termination setting
0
Other than below
1
Last unit on RS485 communication bus
Summary of Contents for PCG-06
Page 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Page 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Page 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Page 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Page 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Page 43: ...HYDRONIC CASSETTE 43 ...
Page 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Page 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Page 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Page 66: ...HYDRONIC CASSETTE 66 ...