HYDRONIC CASSETTE
49
11) Networking Master - Slave control (only master unit wall pad can control other units on the
network)
Press
NET
button to enter into networking control mode. Unit area blinking indicates the slave unit
under control. Press
TIME
or
TIME
to select the desired slave unit; Units that are off will be bypassed
automatically. Parameters that can be controlled are on/off, timer weekly program, set temperature,
mode, fan speed, swing and sleep. Parameter operation methods are the same as above. Press
NET
button again to exit networking control mode.
Hold down
SWIN
G
and
FRESH
buttons for 3 seconds to enter into global control mode,
lights up.
Repeat the same to exit global control mode. In global control mode, the settings of the master unit
will be broadcast to all the slave units.
12) Unit operation parameters browsing
Hold down
CANCEL
and
FAN
buttons for 3 seconds to enter into operation parameters browsing
mode. Unit display area shows the slave unit under browsing. Slave unit selection method is the
same as in networking control above. Press
HUMIDIFY
or
HUMIDIFY
to browse various
parameters as follow:
Wall pad display temperature area
Wall pad display time area
C0
Return air temperature displayed
C1
Indoor coil temperature displayed
C2
DIP switch setting displayed
C3
Indoor coil 2 temperature
Press
CANCEL
button to exit.
13) Error indication
When faulty slave unit is detected, Master unit display area shows the faulty unit address, time area
shows the error code and wall pad backlight changes to red color. Should there be multiple units
having problems, addresses and error codes will be shown one after another.
Error code definition:
Error Error
code
Electrical heater faulty
E1
Indoor coil sensor 2 faulty
E2
Return air sensor faulty
E3
Indoor coil sensor 1 faulty
E4
Indoor coil low temperature protection E5
Indoor coil over heat protection
E6
Water pump faulty
E7
Local communication error
E8
For system without master-slave settings, wall pad will indicate unit error codes as above.
PARAMETER
PARAMETER
Summary of Contents for PCG-06
Page 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Page 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Page 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Page 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Page 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Page 43: ...HYDRONIC CASSETTE 43 ...
Page 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Page 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Page 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Page 66: ...HYDRONIC CASSETTE 66 ...