Index2:
1. Outdoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
For other models:
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
140V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5-16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
15V
Summary of Contents for FS2MIF-140AE2
Page 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Page 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Page 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Page 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Page 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Page 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Page 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...