16
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage
points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump.
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Summary of Contents for FS2MIF-140AE2
Page 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Page 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Page 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Page 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Page 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Page 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Page 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...