![Fisher FS2MIF-140AE2 Service Manual Download Page 40](http://html.mh-extra.com/html/fisher/fs2mif-140ae2/fs2mif-140ae2_service-manual_2294422040.webp)
39
For other models:
NO.
Color
1
Red
2
---
3
Black
4
White
5
Yellow
6
Blue
For console:
5
4
6
3
2
1
NO.
Color
1
Red
2
---
3
White
4
Blue
5
Yellow
6
Black
Index2:
1: Indoor AC fan motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the
voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V
power supply), the PCB must have problems and need to be replaced.