9. Troubleshooting
9.1
Indoor unit error code explanation:
PROFESSIONAL HEAT R series:
Display
Operation lamp flash times Timer lamp
Failure
E0
1
X
Indoor EEPROM malfunction
E1
2
X
Indoor / outdoor units communication error
E3
4
X
Indoor fan speed has been out of control
E4
5
X
Open or short circuit of T1 temperature sensor
E5
6
X
Open or short circuit of T2 temperature sensor
F1
2
O
Open or short circuit of T4 temperature sensor
F2
3
O
Open or short circuit of T3 temperature sensor
F3
4
O
Open or short circuit of T5 temperature sensor
F4
5
O
Outdoor EEPROM parameter error
F5
6
O
Outdoor fan speed out of control
F6
7
O
Open or short circuit of T2B temperature sensor
P0
1
☆
IPM module protection
P1
2
☆
Voltage protection
P4
5
☆
Inverter compressor drive protection
P5
6
☆
Mode conflict
P6
7
☆
Low pressure protection(Just matching with
FS4MIF-360AE2)
O
(
light
)
X
(
off
)
☆
(
flash
)
Light Commercial series(Except Console)
NO.
MALFUNCTION
RUN
Timer
DEF
Alarm
DISPLAY
DIGITAL TUBE
1
Open or short circuit of T1 temperature sensor
☆
X
X
X
E0
2
Open or short circuit of T2 temperature sensor
X
X
☆
X
E1
3
Indoor / outdoor units communication error
X
☆
X
X
E2
4
Full-water malfunction
X
X
X
☆
E3
5
Indoor EEPROM malfunction
☆
☆
X
X
E4
6
IPM module protection
☆
X
X
O
E5
7
Open or short circuit of T3 or T4 temperature sensor or
Outdoor EEPROM malfunction
☆
O
X
X
E6
8
Outdoor fan speed has been out of control
☆
O
☆
X
E7
9
Indoor fan speed has been out of control
☆
O
O
X
F5
10
Voltage protection
☆
O
X
O
P0
12
Outdoor unit over-current protection
☆
☆
☆
X
P2
13
Inverter compressor drive protection
☆
◎
X
X
P4
14
Mode conflict
☆
X
O
O
P5
☆
Flash(at 2.5Hz)
◎
Flash(at 0.5Hz) O light X
(
off
)
Note: Digital display is only available for A5 duct type.
Summary of Contents for FS2MIF-140AE2
Page 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Page 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Page 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Page 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Page 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Page 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Page 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...