2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Summary of Contents for FS2MIF-140AE2
Page 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Page 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Page 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Page 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Page 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Page 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Page 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Page 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Page 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...