R32 ATW Service Manual
68
Press query button to enter spot check. Press up and down button to turn pages.
No.
Display content
Remarks
1
AC side setting water temperature Ts1
2
Domestic hot water setting temperature Ts2
When hydronic module is without
DHW function, it will show 0.
3
Water inlet temperature of heat exchanger Tw_in
4
Water outlet temperature of heat exchanger Tw_out
5
Water outlet temperature of hydronic module T1
6
Ambient temperature T4
7
Temperature detected by temperature probe of wired controller T6
8
Water tank temperature T7
When hydronic module is without
DHW function, it will show 0.
9
Capacity of hydronic module
Capacity (HP) = value * 0.1
10
Operating capacity demand of hydronic module
Capacity (HP) = value * 0.1
11
Water pump gear
14.2 Error code and troubleshooting
14.2.1 Outdoor unit
Code
Failure or protection
Failure cause and corrective action
E1
Three-phase supply phase-sequence
fault
(only for 3Ph unit)
1. Check the power supply cables to avoid phase loss
2. Check the power supply cables sequence; change any two
cables sequence of the three power supply.
E2
Communication
failure
between
indoor unit and outdoor unit
Cause: Communication interrupted f or 2mins or more
between ODU and IDU
1. Wire doesn’t connect between IDU and ODU. Connect the
wire.
Summary of Contents for FHIF-WHS-120CE3
Page 2: ......
Page 9: ...R32 ATW Service Manual 7 1 2 2 Hydronic module FHIF WHS 120CE3 FHIF WHS 160CE3...
Page 18: ...R32 ATW Service Manual 16 Pic 4 3 Domestic hot water mode operation range...
Page 23: ...R32 ATW Service Manual 21 8 System diagram...
Page 28: ...R32 ATW Service Manual 26 Main PCB 3 Hydronic module Main PCB...
Page 29: ...R32 ATW Service Manual 27 Filter board...
Page 34: ...R32 ATW Service Manual 32 Model FHOF WHS 160CE3 3F...
Page 35: ...R32 ATW Service Manual 33 Single unit installation More than one unit installation Unit mm...
Page 46: ...R32 ATW Service Manual 44 HEATING MODE COOLING MODE...
Page 47: ...R32 ATW Service Manual 45 HEATING MODE WITHOUT COOLING MODE DHW MODE WITHOUT COOLING MODE...
Page 48: ...R32 ATW Service Manual 46 HEATING MODE WITHOUT DHW MODE AND DHW TANK ONLY DHW MODE...
Page 56: ...R32 ATW Service Manual 54 When the unit has error code alarm port has a 220V output...
Page 59: ...R32 ATW Service Manual 57...