![Fisher FHIF-WHS-120CE3 Service Manual Download Page 13](http://html1.mh-extra.com/html/fisher/fhif-whs-120ce3/fhif-whs-120ce3_service-manual_2294708013.webp)
R32 ATW Service Manual
11
Air side heat
exchanger
Tube pitch(a)× row
pitch(b)
mm
25×21.7
Tube dia. and type
Φ9.52 inner grooved
copper
Fin space
mm
1.6
Fin type (code)
Hydrophilic
aluminum
Coil
length×height×width
mm
995×1350×43.3
Number of circuits
7
Piping connections
Liquid pipe
Type
Flaring
Dia.(OD)
mm
Φ9.52
Gas pipe
Type
Flaring
Dia.(OD)
mm
Φ15.88
Max. piping length
m
50
Max. height
difference
Outdoor unit upside
m
20
Outdoor unit
downside
m
20
Refrigerant
Type
R32
Quantity
kg
3.8
Throttle type
EXV
Additional charge
g
(Total pipe length - 5)m *30g/m
Ambient temperature
range
Cooling
℃
-5
~
46
℃
Heating
℃
-28
~
43
℃
Sanitary hot water
℃
-28
~
43
℃
Water temperature
range
Cooling
℃
5~25
℃
Heating
℃
25~60
℃
Sanitary hot water
℃
40~60
℃
Note:
Water flow 0.172m^3/(h·kW)
Integrated value takes into consideration the capacity drop during frosting and defrosting periods.
The capacity is tested in free frequency situation.
Summary of Contents for FHIF-WHS-120CE3
Page 2: ......
Page 9: ...R32 ATW Service Manual 7 1 2 2 Hydronic module FHIF WHS 120CE3 FHIF WHS 160CE3...
Page 18: ...R32 ATW Service Manual 16 Pic 4 3 Domestic hot water mode operation range...
Page 23: ...R32 ATW Service Manual 21 8 System diagram...
Page 28: ...R32 ATW Service Manual 26 Main PCB 3 Hydronic module Main PCB...
Page 29: ...R32 ATW Service Manual 27 Filter board...
Page 34: ...R32 ATW Service Manual 32 Model FHOF WHS 160CE3 3F...
Page 35: ...R32 ATW Service Manual 33 Single unit installation More than one unit installation Unit mm...
Page 46: ...R32 ATW Service Manual 44 HEATING MODE COOLING MODE...
Page 47: ...R32 ATW Service Manual 45 HEATING MODE WITHOUT COOLING MODE DHW MODE WITHOUT COOLING MODE...
Page 48: ...R32 ATW Service Manual 46 HEATING MODE WITHOUT DHW MODE AND DHW TANK ONLY DHW MODE...
Page 56: ...R32 ATW Service Manual 54 When the unit has error code alarm port has a 220V output...
Page 59: ...R32 ATW Service Manual 57...