background image

Panel Generator Control P6+ RE0703_Kunde_eng.R10

10.5.17

Generator Control Panel P6+ Manual

12 V version - 0000139

 24 V special version - 0000527

Option automatic adapter - 0000521

Option master-slave adapter - 0000133

Summary of Contents for 0000139

Page 1: ...el Generator Control P6 RE0703_Kunde_eng R10 10 5 17 Generator Control Panel P6 Manual 12 V version 0000139 24 V special version 0000527 Option automatic adapter 0000521 Option master slave adapter 0000133 ...

Page 2: ...3104 Paderborn reserves all rights regarding text and graphics in this document Details are given to the best of our knowledge No liability is accepted for correctness Please note technical modifications aimed at improving the product may be implemented without prior notice Therefore it must be ensured prior to installation that the pictures diagrams and related material are applicable to the gens...

Page 3: ... 14 2 3 4 4 Configuration and setting sheet KE04 15 2 4 Starting preparation Checks daily 16 2 4 1 Marine version 16 2 4 2 Vehicle version 16 2 5 Starting and stopping the generators 17 2 5 1 Starting the generator 17 2 5 2 Stopping the generator 18 2 6 Automatic adapter optional 19 2 6 1 Function 19 2 6 2 The Automatic input 20 2 6 3 Terminal connections 21 2 7 Master Slave adapter optional 21 2 ...

Page 4: ...Seite Page 4 Kapitel Chapter 1 10 5 17 Leere Seite Intentionally blank ...

Page 5: ... not be put into operation with cover removed If the generator is mounted without sound cover the rotating parts pulley belt etc must be covered and protected so that an injury is excluded All service maintenance or repair work on the unit may be made only while the motor is off Warning Danger of Life High voltage Danger for Life Improper handling operation installation and maintenance can result ...

Page 6: ...Safety Instructions Generator Control P6 Seite Page 6 Kaptitel Chapter 1 Safety Instructions Generator Control P6 10 5 17 Note Note also the safety of the other components of your system ...

Page 7: ...D for coolant temperature red1 02 LED for water leak red yellow1 sensor optional 03 LED for AC voltage fault red yellow1 04 LED for AC voltage ok green1 05 LED for winding temperature red1 06 LED for oil pressure red1 07 LED for battery charge voltage fault green red1 08 LED for pre glow heat orange1 09 LED for Generator start green1 10 LED for Generator stand by green1 11 Push button for pre glow...

Page 8: ...iew 12 V version Fischer Panda Art No 21 02 02 046P Fig 2 1 1 Panel rear view 12 V version 02 01 03 04 01 Control board 02 Terminal block master slave adapter left row automatic adapter right row 03 Terminals 1 12 see section 2 3 2 Terminal connections on page 10 04 Fuse 630 mA slow blow ...

Page 9: ... Art No 21 02 02 047P Fig 2 2 1 Panel rear view 24 V version 02 01 04 05 06 03 01 Control board 02 Terminal block master slave adapter left row automatic adapter right row 03 Fuse 630 mA slow blow 04 Terminals 1 12 see section 2 3 2 Terminal connections on page 10 05 Linear controller 24 V 06 Linear controller 24 V ...

Page 10: ...r 12 V 24 V OK must be adjusted by solder Jumper The input loads the signal with 5 mA at 12 V and 10 mA at 24 V The input status is indicated with red and green LED The connection can supply an energizing current for the dynamo over a fixed resistor with 68R Either with the control panel switched on or with Fuel pump switched on must be adjusted by solder Jumper This function is available only in ...

Page 11: ...rated open Function deactivated J3 1 2 Dynamo excitation resistor 68R is switched on with Fuel Pump 1 2 3 Dynamo excitation resistor 68R is switched on with Panel ON 1 open Dynamo excitation resistor is deactivated J101 closed 12 V operation open 24 V operation optional J201 1 2 T Engine input for contact which opens in case of error 2 2 3 T Engine input for contact which closes in case of error 2...

Page 12: ...X 12 V operation open 24 V operation not possible J201 1 2 X T Engine input for contact which opens in case of error 2 2 3 T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 X Water leak input Replace air filter for contact which closes in case of error 2 J203 1 2 X Oil Press input for contact which...

Page 13: ... J101 closed 12 V operation open X 24 V operation J201 1 2 X T Engine input for contact which opens in case of error 2 2 3 T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 X Water leak input Replace air filter for contact which closes in case of error 2 J203 1 2 X Oil Press input for contact which...

Page 14: ...n not possible J201 1 2 X T Engine input for contact which opens in case of error 2 2 3 T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 X Water leak input Replace air filter for contact which closes in case of error 2 J203 1 2 X Oil Press input for contact which opens in case of error 2 2 3 Oil P...

Page 15: ... closed 12 V operation closed X 24 V operation J201 1 2 X T Engine input for contact which opens in case of error 2 2 3 T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 X Water leak input Replace air filter for contact which closes in case of error 2 J203 1 2 X Oil Press input for contact which op...

Page 16: ... checked and cleaned The impeller fatigue increases if residual affects the raw water intake 5 Visual inspection Control fixing bolts check hose connectors for leakages control electrical connections 6 Switch off the load The generator should only be started without load 7 Open fuel valve if installed 8 Close battery main switch on 2 4 2 Vehicle version 1 Oil level control ideal level 2 3 MAX The ...

Page 17: ...pon engine type and execution pre heating can be necessary Pre heat is necessary at an operating temperature 20 C Fig 2 5 1 3 Start 3 Press button start start engine LED for start green The electric starter may only be used for a maximum of 20 seconds Thereafter a pause of at least 60 seconds is required If the genset does not immediately start then the fuel intake should be checked to ensure it i...

Page 18: ...hich has been brought to the exhaust outlet To avoid filling the exhaust outlet with water and causing further problems close the inlet sea water valve Once the engine is running be sure to open the inlet valve 2 5 2 Stopping the generator 1 Switch off load 2 Recommendation With turbo engines and during load more than highly 70 of the rated output stabilize generator temperature at least 5 minutes...

Page 19: ...ic stop procedure can be terminated only by switching off generator control panel prematurely The times for heat start and stop are separately adjustable see below The additional automatic adapter switched on and off using the generator control panel with its push buttons on and off If the contact at the automatic input is connected while the generator control panel is switched on then the automat...

Page 20: ...Fig 2 6 2 2 Settings Attention The automatic adapter must only be used together with an additional device The starter should only be switched on when the generator stationary shut down Data Parameter Information Operation voltage The automatic adapter power is supplied via the generator control panel P6 The same absolute maximum ratings obtain as with the generator control panel P6 Operation tempe...

Page 21: ...nected with VBFS at optional 24 V operation VBFS over internal voltage regulator at 12 9 V regulated 9 GND O power supply ground 11 GND O power supply ground 13 Heat signal I Heat is active if the input is switched to GND 15 Start signal I Start is active if the input is switched to GND 17 GND O power supply ground 19 GND O power supply ground 21 GND O power supply ground 23 GND O power supply gro...

Page 22: ...on the Slave Panel are coded as for slave operation please see the appropriate adjustment pages for the Generator Control Panel P6 RE0703 The Master Panel and Slave Panel are identical and only differs as a result of the coding Both Master Slave Panels are also identical 2 7 3 Terminal connections X2 14polig 21 34 master Slave connection 1 1 wire X3 2polig 35 36 35 Panel on signal of the Generator...

Page 23: ...ed using a push button on master or slave to VBF 24 OFF Signal I O Panels are switched off if the connection is switched using a push button on master or slave to VBF 25 Heat Signal I O Heat is active if the connection is switched over a push button on master or Slave to GND 26 Start Signal I O Start is active if the connection is switched over a push button on master or Slave to GND 27 LED T Engi...

Page 24: ...r 68R is switched on with Panel ON 1 open XM Dynamo excitation resistor is deactivated J101 closed M 12 V operation open M 24 V operation not possible J201 1 2 T Engine input for contact which opens in case of error 2 2 3 XM T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 XM Water leak input Repl...

Page 25: ...Dynamo excitation resistor 68R is switched on with Panel ON 1 open XM Dynamo excitation resistor is deactivated J101 closed M 12 V operation open M 24 V operation J201 1 2 T Engine input for contact which opens in case of error 2 2 3 XM T Engine input for contact which closes in case of error 2 J202 1 2 Water leak input Replace air filter for contact which opens in case of error 2 2 3 XM Water lea...

Page 26: ...Seite Page 26 Kapitel Chapter 2 General operation 10 5 17 Leere Seite Intentionally blank General operation ...

Page 27: ...r Ersetzt durch Blatt Panel Generator Control 06 03 2007 jschaefers 1 A3 Otto Hahn Str 32 34 D 33104 Paderborn Tel 05254 9202 0 Fax 05254 85724 info fischerpanda de www fischerpanda de Allgemeintoleranzen nach DIN ISO 2768 mK Halbzeug Schutzvermerk nach DIN 34 beachten 2D Zeichnungs Nr 7067e01 Q Zeichnungen 7067e01 idw Alle nicht bemaßten Fasen a 0 5 mm 25 105 195 95 185 Q 3 5 4 x 185 95 88 177 Sk...

Page 28: ...Seite Page 28 Kapitel Chapter 3 Measurements 10 5 17 Leere Seite Intentionally blank Measurements ...

Reviews: