General operation
10.5.17
Kapitel/Chapter 2: General operation - Seite/Page 19
2.6
Automatic adapter - optional
Fischer Panda Art. No. 21.02.02.016P
Fig. 2.6-1: Panel 21.02.02.046P with Automatic adapter 21.02.02.016P
2.6.1 Function:
The automatic adapter RE0704 extends the generator control panel P6+ with an automatic input. A potential-free
contact can be attached to this input. If this contact is closed, then the generator, which is attached to the generator
control panel P6+, is started automatically. If the contact is opened, then the generator is stopped automatically.
The automatic starting procedure consists of pre-heating (heat) and operating the starter (start). It can be again
aborted at any time by opening the contact at the automatic input.
For automatic stopping (stop) the output “Fuel pump” (clamp 9 generator control panel) is switched off. The time for
the automatic stop procedure can be terminated only by switching off generator control panel prematurely.
The times for “heat”, “start” and “stop” are separately adjustable (see below).
The additional automatic adapter switched on and off using the generator control panel with its push buttons “on”
and “off”.
If the contact at the automatic input is connected, while the generator control panel is switched on, then the
automatic starting procedure is carried out.
If the power supply is attached or switched on using the generator control panel, while the contact of the automatic
input is closed, then the automatic starting procedure won't be carried out, because the generator control panel is
always switched off after attaching the power supply (generator the control panel must have been separate from the
power supply for at least 60 s).
Attention!
If the contact at the automatic input is closed and if the
panel is switched on again after a voltage drop, the
automatic start (glow, start) will be introduced.
01
02
03
01. Main terminals
02. Automatic adapter 21.02.02.016P
03. 8-pole DIP-switch