Adjustments menu
In the adjustments menu (AJUS) you must enter the required setpoint values according to
the operating mode and configuration selected.
In this menu, the configuration setpoints and additional
batteries are adjusted.
Press
to enter the menu. Using the keys
and
you
can navigate through the menu screens. Press
if you
want to change a setpoint. When the digit flashes, adjust its
value with the keys
and
; you can return to this
screen with the
key.
Apply in "S" stages configuration
The H2 and H3 interlocks control the reactivation battery in
two stages.
In H3 the desired percentage of power of the second stage
is adjusted, therefore, the percentage of the first stage is:
H2(100%) minus H3 (%) = 1st stage %
Apply in measurement signal configuration "M":
a) If you have selected the RH [%] adjustment menu
Adjust the desired relative humidity setpoint between 0%
and 100%.
The second figure is a maximum humidity alert.
b)
The alarm is triggered when the value measured by the
humidity probe SH1 is higher than the sum total of the
humidity setpoint and the differential margin for the
maximum humidity alarm.
c) If you have selected theTdp [°C] adjustment menu
Adjust the desired dew point between -40°C and +20°C
The second figure is a maximum humidity alert.
The alarm is triggered when the value measured by the dew
point probe is higher than the sum total of the dew point
setpoint and the humidity alarm.