First Co 12MB-HW Installation, Operation & Maintenance Instructions Manual Download Page 14

16-pin Plug on Select Control Board

1. Unplug wiring harness from board.

2. Check for appropriate voltage on connector pins with Select Control Board terminals jumpered.  See table

2 for values and example below.

If proper signals are not present, replace the Select Control Board. If signals are present at the board and not the

other end of the wiring harness, the wiring harness is defective.

TROUBLESHOOTING EXAMPLE:

Motor is not running on a call for cooling.

1.  After performing checks in Thermostat section, follow steps 1 thru 5 in the Wiring Harness section.  Then proceed

with the example.

2.  With all thermostat wires removed from the Select Control board, place a jumper wire between R and Y1 low

voltage terminals on the Select Control board.

3.  Check table 2 for pin number on the 16-pin connector associated with the Y signal.  The correct pin is #6.  The far

right column shows that(-) 12VDC should be present between pin #6 and pin #1 (common) on the 16-pin

connector.

4.  Set meter to read DC voltage.  Place meter between pins #1 and #6 and check for (-) 12VDC (common side of meter

on pin #1.)  If signal is present, the problem is the module or motor.  If signal is not present, then problem is either

wiring harness or Select Board.

These steps can be repeated for the other modes of operation.

To check Select Control Board:

1.  Leave jumper wire in place between R and Y1.

2.  Remove 16-pin wiring harness from the Select Control Board.

3.  Check table 2 for pin number on the 16-pin connector associated with the Y signal.  The correct pin is #6.  The far

right column shows that(-) 12VDC should be present between pin #6 and pin #1 (common) on the 16-pin socket

connector.

4.  Place meter between pins # 6 and #1 on the socket connector and check for (-) 12VDC.

5.  If voltage is present, the wiring harness is bad.  If not, the Select control Board is bad.

D.  Verify Motor Winding Section:

Before proceeding with module replacement, check the following to ensure motor winding section is functional.  With

control module removed and unplugged from the winding section:

1.  The resistance between any 2 motor leads should be similar.

2.  The resistance between any motor lead and unpainted motor end plate should be greater than 100K ohms.

3.  If motor winding section fails one of these test, it is defective and must be replaced.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be

performed on this equipment.  For a current copy of the detailed Maintenance Program, log on to 

www.firstco.com

 and look

under “Product Information”.

WARNING:  

Disconnect all power to unit before servicing field wires or removing control package.  The

disconnect (when used) does not disconnect power to the line side of the disconnect, but does allow safe

service to all other parts of the unit.  If the unit does not have a disconnect, disregard the foregoing.  Instead,

make sure that a disconnecting means is within sight from, and is readily accessible from, the unit.  Discon-

nect all power to the unit before performing any maintenance or service on it.   Failure to follow this
WARNING can cause electrical shock, fire, personal injury or death.

The minimum maintenance requirements for this equipment are as follows:

1.  Inspect and clean or replace the air filter every 30 days or more frequently if severe conditions exist.  Always replace

the filter with the same type as originally furnished.

2.  Inspect cooling coil before each cooling season. The coils must be kept clean, any dust or other contaminants which

accumulate on the heat transfer surfaces interferes with the air flow and impairs heat transfer.  The coil can be

cleaned by one of the following methods: Cleaning with low pressure compressed air or flushing and rinsing with

water and a detergent is advisable for greasy surfaces.

14

Summary of Contents for 12MB-HW

Page 1: ...al for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...or brazing to the unit it is recommended to have a fire extinguisher readily available When soldering close to valve packages or other components heat shields or wet rags are required to prevent damag...

Page 3: ...condensate pan 2 When suspending unit from ceiling with metal support straps extreme care should be taken that no internal damage will result if screws are drilled into the cabinet CAUTION The unit sh...

Page 4: ...ing label for proper field high and low voltage wiring Make all electrical connec tions in accordance with NEC and any local codes or ordinances that may apply Use copper wire only The unit must have...

Page 5: ...r piping prior to connection to water coils to remove debris Use wet cotton rags to cool valve bodies when soldering Open all valves midway for hand valves manually open on motorized valves prior to s...

Page 6: ...inal 1 1 8 OD The hot water supply to the fan coil will be on the right when facing the fan coil upright and from the front All piping between the water heater and fan coil unit should be copper and s...

Page 7: ...roper drainage CAUTION Shallow running traps are inadequate and DO NOT allow proper condensate drainage See figure 6 Failure to follow this CAUTION could result in product and property damage NOTE If...

Page 8: ...requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible Make sure that the outlet of each trap is below its connection to the condensate pa...

Page 9: ...to modify its operation to a pre programmed table of airflows See Table 1 Airflows are based on the system size or mode of operation and those airflows are modified in response to other inputs such as...

Page 10: ...Mild Humid Climates the motor is programmed with ramp time and speed to achieve dehumidification on cooling start up thus allowing more moisture to collect and drain from the coil The off cycle delay...

Page 11: ...et point and humidity is above humidity set point if dehumidistat is installed thermostat closes circuit R to G and R to Y1 and dehumidistat opens R to HUM The fan coil delivers airflow which is appro...

Page 12: ...ltage is present check the transformer 2 Check all plugs and receptacles for any deformation which could cause loose connections Be sure plugs are fully seated 3 Verify that approximately 120VAC is pr...

Page 13: ...rom the motor These signals will start the motor Dehumidify 24VAC is present with a call for no dehumidication Pin on 16 Pin Connector Signal on pin with Screw Terminal Jumpered to R 1 Common 2 W W1 H...

Page 14: ...oard is bad D Verify MotorWinding Section Before proceeding with module replacement check the following to ensure motor winding section is functional With control module removed and unplugged from the...

Page 15: ...an as required 5 Inspect electrical connections for tightness and controls for proper operating each heating and cooling season Service as required WARNING As with any mechanical equipment personal in...

Reviews: