First Co 12MB-HW Installation, Operation & Maintenance Instructions Manual Download Page 10

NOTE: 

 The unit may appear to ‘pulse’ with system static pressures greater than 0.5 in H2O.

The fan coil must be configured to operate properly with system components with which it is installed.  To successfully

configure a basic system select the proper setting of the four Select Taps.

Cooling Select Tap –

 Select system airflow for cooling output.  See figure 10.

Refer to Table 1 to select the proper airflow and Select Tap for the chilled water coil installed.  Proper selection should be

derived from BTUH output of the coil from the unit specification sheet.  The typical selection would be 350 to 400 CFM per

ton.

Heating Select Tap –

 Select system airflow for heat output.  See figure 10.

Refer to Table 1 to select the proper airflow and Select Tap for the hot water coil installed.  Proper selection should be

derived from BTUH output of the coil from the unit specification sheet.  The typical selection would be 350 to 400 CFM per

ton.

Adjust Select Tap –

 Select system CFM airflow requirement.  See figure 10.

Adjust select options are provided to adjust airflow supplied to meet individual installation conditions such as noise,

comfort and humidity removal.  To provide airflow at rates described in Table 1, the Adjust Tap is factory set at nominal

(NORM).  The adjust selections will regulate airflow supplied for all operational modes.  The (+) tap provides 10 percent

airflow over nominal airflow selected and the (-) tap provides 10 percent airflow below nominal airflow selected.

Delay Select Tap – 

Select desired delay profiles.  See figure 10.

Four operation delay profiles are provided to customize and enhance system operation.

NOTE:

  

The delay profiles are active only in the cooling modes.

Selection Options:

A

 –  Arid Climates – the motor is programmed with a minimum ramp time to achieve full cooling capacity within a short

time period.  The off cycle delay is programmed with a reduced airflow over an extended time period.

B

 -  Mild Humid Climates – the motor is programmed with ramp time and speed to achieve dehumidification on cooling

start-up, thus allowing more moisture to collect and drain from the coil.  The off cycle delay is programmed with a

reduced airflow and short time period to enhance system efficiency and minimize re-evaporation of condensate.

C

 -  Humid Climates – the motor is programmed with extended ramp time and reduced speed to achieve maximum

dehumidification on cooling start-up, thus allowing more moisture to collect and drain from the coil.  There is no

off cycle delay programmed to eliminate re-evaporation of condensate.

D – 

No Delays – the motor is programmed with no delays to represent normal operation of a standard air handler.

Heat Delay -

 

the motor is factory programmed with a pre-purge time to permit the circulator to circulate hot water to the fan

coil before the blower operates at a reduced CFM.    The off cycle delay is programmed with a reduced airflow over a short

time period to post purge the heat out of the water coil and duct system.

NOTE: The unit does NOT read changes in COOL, HEAT, and DELAY taps while it is running. Disconnect power

for 1 minute before changing taps, then restart for the new settings to take affect.

Dehumidify Capability with Standard Dehumidistat Connection

Latent capacities for systems using the VMB-HW Fan Coil are better than average systems.  If increased latent capacity is

an application requirement, the field wiring terminal block provides connection terminals for use with a standard

dehumidistat.  The fan coil will detect the dehumidistat contacts opening on increased humidity and reduce its airflow to

approximately 80 percent of nominal cooling airflow.  This reduction will increase the system latent capacity until the

humidity falls to a level, which causes the humidistat to close its contacts.  When the contacts close, the airflow will return

to 100 percent of the selected cooling airflow.  To activate this mode, cut the resistor located on the lower right hand corner

of the selection control board and wire in a standard dehumidistat. (Refer to figure 9.)

10

Summary of Contents for 12MB-HW

Page 1: ...al for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...or brazing to the unit it is recommended to have a fire extinguisher readily available When soldering close to valve packages or other components heat shields or wet rags are required to prevent damag...

Page 3: ...condensate pan 2 When suspending unit from ceiling with metal support straps extreme care should be taken that no internal damage will result if screws are drilled into the cabinet CAUTION The unit sh...

Page 4: ...ing label for proper field high and low voltage wiring Make all electrical connec tions in accordance with NEC and any local codes or ordinances that may apply Use copper wire only The unit must have...

Page 5: ...r piping prior to connection to water coils to remove debris Use wet cotton rags to cool valve bodies when soldering Open all valves midway for hand valves manually open on motorized valves prior to s...

Page 6: ...inal 1 1 8 OD The hot water supply to the fan coil will be on the right when facing the fan coil upright and from the front All piping between the water heater and fan coil unit should be copper and s...

Page 7: ...roper drainage CAUTION Shallow running traps are inadequate and DO NOT allow proper condensate drainage See figure 6 Failure to follow this CAUTION could result in product and property damage NOTE If...

Page 8: ...requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible Make sure that the outlet of each trap is below its connection to the condensate pa...

Page 9: ...to modify its operation to a pre programmed table of airflows See Table 1 Airflows are based on the system size or mode of operation and those airflows are modified in response to other inputs such as...

Page 10: ...Mild Humid Climates the motor is programmed with ramp time and speed to achieve dehumidification on cooling start up thus allowing more moisture to collect and drain from the coil The off cycle delay...

Page 11: ...et point and humidity is above humidity set point if dehumidistat is installed thermostat closes circuit R to G and R to Y1 and dehumidistat opens R to HUM The fan coil delivers airflow which is appro...

Page 12: ...ltage is present check the transformer 2 Check all plugs and receptacles for any deformation which could cause loose connections Be sure plugs are fully seated 3 Verify that approximately 120VAC is pr...

Page 13: ...rom the motor These signals will start the motor Dehumidify 24VAC is present with a call for no dehumidication Pin on 16 Pin Connector Signal on pin with Screw Terminal Jumpered to R 1 Common 2 W W1 H...

Page 14: ...oard is bad D Verify MotorWinding Section Before proceeding with module replacement check the following to ensure motor winding section is functional With control module removed and unplugged from the...

Page 15: ...an as required 5 Inspect electrical connections for tightness and controls for proper operating each heating and cooling season Service as required WARNING As with any mechanical equipment personal in...

Reviews: