![First Co 12MB-HW Installation, Operation & Maintenance Instructions Manual Download Page 12](http://html1.mh-extra.com/html/first-co/12mb-hw/12mb-hw_installation-operation-and-maintenance-instructions-manual_2293638012.webp)
PROCEDURE 10 TROUBLESHOOTING ECM MOTOR AND CONTROLS
CAUTION:
High voltage is always present at the motor. Disconnect power to the unit before removing or
replacing connectors or servicing motor. Wait at least 5 minutes after disconnecting power before opening
motor. Failure to follow this CAUTION could result in personal injury or product and property damage.
The ECM motor contains two parts: the control module and motor winding section.
Do not assume the motor or module is
defective if it will not start.
Go through the steps described below before replacing control module, Select Control Board or
entire motor. The control module is available as a replacement part.
A. If motor turns slowly:
1. Replace panel. Motor may appear to run slowly if access panel is removed.
2. It is normal operation to run noticeably slower if G terminal is energized without a call for heat or cooling.
B. If motor does not run:
1. Check for 24VAC at terminal R and C1. If no voltage is present, check the transformer.
2. Check all plugs and receptacles for any deformation, which could cause loose connections. Be sure plugs are fully
seated.
3. Verify that approximately 120VAC is present at the motor.
C. Check control signals:
Verify low voltage control signals to motor. The motor receives its control signals through the 16-pin wiring harness.
The combination of pins energized will determine the motor speed. See table 2 for pin number on 16-pin plug which
should have voltage when Select Control Board screw terminals have 24VAC.
Thermostat
1. Remove all thermostat wires from Select Control board,
2. Jumper screw terminals on the select control board one at a time: R-G, R-Y1, and R-W1. (Note: R-W1 must be
jumpered for at least a minute to see if motor will run.) If motor runs in all cases, thermostat is miswired, config-
ured incorrectly or defective. If motor runs in some cases, but not others, continue to check wiring harness and
circuit board.
R
C1 (RCom)
EM
W1
O
Y2
Y1
G
CFM
FIRST CO. -- CB600
Y2 Y1 G O W1 W2 NC C1 R HUM
EM
HEAT
A
B
C
D
COOL
A
B
C
D
DELAY
A
B
C
D
ADJUST
-
NORM
+
TEST
DEHUMIDIFY
CUT TO ENABLE
Figure 10 - Select Control Board
12