background image

Wiring Harness

1. Shut off power to unit. Wait 5 minutes.

2. Remove 5-pin connector from motor.

3. Remove 16-pin connector from motor.

4. Replace 5- pin plug and turn power on.

5. Check for correct voltages on 16-pin connector with screw terminals jumpered. ( See table 2 for values.)

If signals check correctly and motor does not run, inspect wiring harness for loose pins or damaged plastic connec-

tors that could cause poor connections.  If connections are good, either motor control module or motor is defective.

If proper signals are not present, check Select Control Board using procedure below:

13

Table 2  -  Wiring Harness Terminations

*  Check voltages wit 16-Pin Plug disconnected from the motor.

**  These signals will start the motor.

Dehumidify - 24VAC is present with a call for no dehumidication.

Pin # on     

16-Pin 

Connector

Signal on pin with 

Screw Terminal 

Jumpered to R *

1

Common

2

W /W1

Heating Signal

24VAC **

3

Common

4

Delay Adjust

5

Cool Fan Adjust

6

Y1

Cooling Signal

(-) 12VDC **

7

CFM  Adjust

8

Not  Used

9

"O"    (HP/Cool)

10

Dehumidify

0V (24VAC on no call)

11

Heat Fan Adjust

12

24V  AC

24VAC continuous

13

W2 / EM

Not used

14

Y /Y2

Not Used

15

G

Fan Signal

24VAC **

16

Not Used

Description

16-Pin Motor Wiring Harness to 16-Pin Connector on Select Board

1

4

5

3

2

AC

LINE

AC

LINE

CHASSIS

GROUND

JUMPER PIN 1 TO  PIN 2  FOR

120VAC LINE INPUT ONLY

Figure 11  -  5 Pin Power Connector

Figure 10  -  16 Pin Signal Connector

1

2

3

4

6

5

7

8

9

10

11

12

14 13

15

16

Y1

C W1 C

G

24V

DH

WARNING:

  Applying 240VAC line input

with Pin 1 and Pin 2 jumper in place

will permanently damage unit.

Summary of Contents for 12MB-HW

Page 1: ...al for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...or brazing to the unit it is recommended to have a fire extinguisher readily available When soldering close to valve packages or other components heat shields or wet rags are required to prevent damag...

Page 3: ...condensate pan 2 When suspending unit from ceiling with metal support straps extreme care should be taken that no internal damage will result if screws are drilled into the cabinet CAUTION The unit sh...

Page 4: ...ing label for proper field high and low voltage wiring Make all electrical connec tions in accordance with NEC and any local codes or ordinances that may apply Use copper wire only The unit must have...

Page 5: ...r piping prior to connection to water coils to remove debris Use wet cotton rags to cool valve bodies when soldering Open all valves midway for hand valves manually open on motorized valves prior to s...

Page 6: ...inal 1 1 8 OD The hot water supply to the fan coil will be on the right when facing the fan coil upright and from the front All piping between the water heater and fan coil unit should be copper and s...

Page 7: ...roper drainage CAUTION Shallow running traps are inadequate and DO NOT allow proper condensate drainage See figure 6 Failure to follow this CAUTION could result in product and property damage NOTE If...

Page 8: ...requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible Make sure that the outlet of each trap is below its connection to the condensate pa...

Page 9: ...to modify its operation to a pre programmed table of airflows See Table 1 Airflows are based on the system size or mode of operation and those airflows are modified in response to other inputs such as...

Page 10: ...Mild Humid Climates the motor is programmed with ramp time and speed to achieve dehumidification on cooling start up thus allowing more moisture to collect and drain from the coil The off cycle delay...

Page 11: ...et point and humidity is above humidity set point if dehumidistat is installed thermostat closes circuit R to G and R to Y1 and dehumidistat opens R to HUM The fan coil delivers airflow which is appro...

Page 12: ...ltage is present check the transformer 2 Check all plugs and receptacles for any deformation which could cause loose connections Be sure plugs are fully seated 3 Verify that approximately 120VAC is pr...

Page 13: ...rom the motor These signals will start the motor Dehumidify 24VAC is present with a call for no dehumidication Pin on 16 Pin Connector Signal on pin with Screw Terminal Jumpered to R 1 Common 2 W W1 H...

Page 14: ...oard is bad D Verify MotorWinding Section Before proceeding with module replacement check the following to ensure motor winding section is functional With control module removed and unplugged from the...

Page 15: ...an as required 5 Inspect electrical connections for tightness and controls for proper operating each heating and cooling season Service as required WARNING As with any mechanical equipment personal in...

Reviews: