3
Table 2:
LOAD RATINGS: All Ratings are 120V, 60 Hz
Table 3:
ALTERNATIVE LOAD RATINGS:
Table 4:
COMPOSITION OF EACH COMBINATION
Fireye Terminal
Typical Load
Maximum Rating @120V 60 Hz
3 or 4
Individual or combined
Pilot valve(s)
Solenoid valve
Ignition Transformer
125 VA pilot duty (solenoid valve) plus
250 VA (Transformer)
5
Main Fuel Valve(s)
125 VA pilot duty (solenoid) or
25 VA pilot duty (solenoid) and
400 VA (opening) motorized, 250 VA hold
8
Motor or contactor
Terminal 8 rated to energize and de-energize 9.8 FLA,
58.8 LRA on safety lockout.
A
Alarm
125 VA, pilot duty
Minimum load requirement = 100mA
COMBINATION NUMBER
PILOT FUEL TERMINAL 3
IGNITION TERMINAL 4
MAIN VALVE TERMINAL 5
1
C
NO LOAD
E
2
B
NO LOAD
E
3
NO LOAD
NO LOAD
E
4
E
A
E
5
NO LOAD
A
E
6
D
A
E
7
D
A
D
8
NO LOAD
A
D
A
B
C
D
E
4.5A Ignition
50 VA Pilot Duty
plus 4.5A ignition
180 VA Ignition
plus motor values
with: 600VA
inrush., 360 VA
open, 250 VA hold
2A Pilot Duty
65 VA Pilot Duty
plus Motor valves
with: 3850 VA
in rush., 700 VA
open, 250 VA hold