7
MicroM Programmer Models (For use with MEC320 and MEC 480 Chassis)
MEP300
Relight operation, 10 sec. fixed PTFI, 5 second pilot proving period, 5 second MTFI. lockout on flame fail during PTFI,
pilot proving and MTFI. Recycle on air flow open. No post purge. Reset on line voltage.
MEP304
Non-recycle on flame fail, 5 second purge, 10 second fixed PTFI, 5 second pilot proving, 10 second MTFI, interrupted
pilot, early spark termination.
MEP397
Recycle on main flame fail, 15 second purge, 7 second fixed PTFI, 5 second pilot proving 5 second MTFI, early spark
termination and interrupted pilot. Recycle on air flow failure. No post purge, run/check switch. Reset on line voltage.
MicroM Amplifier Models:
MEUV1
UV amplifier, 0.8 second FFRT, uses UV1A, UV2, UV8A, UV90 and 45UV3-1050 scanners.
MEUV4
UV amplifier, 3 second FFRT, uses UV1A, UV2, UV8A, UV90 and 45UV3-1050 scanners.
MEUVS1
UV Self-Check amplifier, 0.8 second FFRT, uses 45UV5-1009 scanner.
MEUVS4
UV Self-Check amplifier, 3 second FFRT, uses 45UV5-1009 scanner.
MERT1
Flame Rod / Photocell amplifier, 0.8 second FFRT, uses 69ND1 or 45CM1.
MERT4
Flame Rod / Photocell amplifier, 3 second FFRT, uses 69ND1 or 45CM1.
MEIR1
Infrared amplifier, 0.8 second FFRT, uses 48PT2 scanner.
MEIR4
Infrared amplifier, 3 second FFRT, uses 48PT2 scanner.
MECD1
Cadmium sulfide amplifier, 0.8 second FFRT, uses CS1A5 scanner.
MECD4
Cadmium sulfide amplifier, 3 second FFRT, uses CS1A5 scanner.
MEDC2
Dry contact amplifier, for use with MEP237.
Optional Plug-In Board Modules:
MED1
Standard local reset switch.
MED2
Same as MED1 with display output.
MED3
Same as MED1 with remote reset.
MED4
Same as MED1 with display output and remote reset.
MED5
Same as MED1 with display output and communications.
MED6
Same as MED1 with display output, remote reset and communications.
MED7
Same as MED1 with communications.
Wiring Base (Common for all Controls):
61-3060
Closed wiring base, surface mounting.
61-5042
Open wiring base, cabinet mounting.
Accessories
ED510
Two line by 16 character, back lit LCD display with keypad.
ED580-2, -4, -8
Remote display cable with RJ45 connection in 2, 4 or 8 foot long lengths. To be used with the appropriate daughter
board.
EC485
RS232/RS485 converter with power supply and RJ12 jack.
SMDK-1004
Serviceman’s display kit used for diagnosing MicroM system. Consists of ED510 equipped with back plate, MED
daughter board and ED580-4.
129-145-1, -2, -3
ED510 remote display mounting kit with 4’, 8’ or 2’ cable respectively. Provides NEMA 4 protection.
IT1000
Monitoring device using cellular networks. Provides various reporting methods