Addressing Modes
For communication in a multi-burner or multi-control environment, each MicroM must have a
unique address. The range of address allowed within the MicroM is 0 to 31 allowing for a possible 32
units to be connected in a single multi-drop node. As shipped the default address is 0. The address of
the MicroM may be set using two methods. Using the ED510 display, it is necessary is SCRL to the
PROGRAM SETUP menu and enter that submenu with the MODE key. SCRL down until the dis-
play indicates UNIT ADDRESS with the actual address of the MicroM being displayed on the top
line of the display. Pressing and releasing the RESET key will cause the address to increment. The
Table 3: Message Description
DEC
HEX
MicroM Message
1
1
L1-7 OPEN
2
2
FALSE FLAME
3
3
STARTING BURNER
4
4
5
5
INTRLCK OPEN
6
6
LOCKOUT LINE FREQUENCY NOISE DETECTED
7
7
LOCKOUT FLAME FAIL - PTFI
8
8
UNIT ADDRESS
9
9
MTFI
10
0AH
IGNITION TIMING
11
0BH
12
0CH
FLAME SIGNAL
13
0DH
CYCLE COMPLETE
14
0EH
OFF
16
10H
LOCKOUT AMPLIFIER HIGH COUNT FAIL
19
13H
LOCKOUT FLAME FAIL – MTFI
20
14H
LOCKOUT FALSE FLAME – STANDBY
21
15H
LOCKOUT INTRLCK OPEN
22
16H
LOCKOUT INTRLCK CLOSED
23
17H
INTRLCK CLOSED (PROVING AIR FLOW OPEN AT START)
24
18H
LOCKOUT OPTO FAILURE
30
1EH
FALSE FLAME
37
25H
LOCKOUT FLAME FAIL - AUTO
39
27H
FUEL VALVE STATE CHANGE
40
28H
AIR FLOW CLOSED
49
31H
LOCKOUT FLAME FAIL - PTFI
54
36H
LOCKOUT CHECK CHASSIS
55
37H
LOCKOUT CHECK PROGRAMMER
56
38H
LOCKOUT CHECK AMPLIFIER
58
3AH
LOCKOUT AMPLIFIER AUTO CHECK FAIL
59
3BH
LOCKOUT CHECK BLOWN FUSE
76
4CH
LOCKOUT CHECK SCANNER