background image

11

®

FIGURE 3.

ALTERNATE WIRING ARRANGEMENT 

Use moisture resistant wire suitable for at least 90

C.

CAUTION: Control wiring procedures which deviate from those shown in the diagrams may
bypass safety functions designed in the control. Check with the Fireye Representative before
deviating from the recommended wiring diagrams.

S2

3

5

4

MAIN

IGNITION

7

8

2

A

6

STOP

PILOT

S1

START

LIMIT SW

FUEL VALVE

ALARM

ON-OFF

HOT

NEUTRAL

LR-1

LR-2

LATCH

AIR FLOW

SWITCH

MOTOR

A. FOR MANUAL START

A START-STOP STATION MAY BE ADDED TO REQUIRE 

OPERATOR START-UP EACH TIME THE BURNER FIRES.

S2

3

5

4

IGNITION

7

8

2

A

6

PILOT

S1

B. MULTIPLE BURNER SYSTEMS

S2

3

5

4

IGNITION

7

8

2

A

6

PILOT

S1

LIMIT

R

MANUAL RESET

MAIN GAS VALVE

ALARM

S.P.D.T.

RA

ALARM SILENCE

SWITCH

G

R

STOP

START

LR-1

AIR FLOW

COIL OF MOTOR

CONTACTOR

LATCH

HOT

NEUTRAL

MULTIPLE BURNER SYSTEMS UTILIZING SEMI-AUTOMATIC OPERATION INCORPORATE THE FIREYE
MODULAR M-SERIES II CONTROLS IN A CASCADING SEQUENCE WHEN PILOT #1 IS PROVEN. TRIAL
FOR IGNITION FOR PILOT #2 BEGINS. WHEN ALL PILOTS ARE PROVEN THE SAFETY SHUTOFF VALVE
MAY BE MANUALLY OPENED. FLAME FAILURE OF ANY BURNER WILL TRIP THE MAIN FUEL VALVE AND
SOUND ALARM. 
THE TOTAL CONNECTED LOAD MUST NOT EXCEED THE RATING OF THE FIRST CONTROL.

VALVE

RELAY COIL

MAIN GAS VALVE

GAS VALVE

RELAY

GAS VALVE

SWITCH

SWITCH

HOT

Summary of Contents for M4RT1

Page 1: ...e Failure Response Time F F R T is fixed at three seconds LED indicator lights indicate the operat ing status of the control In the event of ignition failure or following a safety shutdown the unit lo...

Page 2: ...D1 1000K8 24 inch flame rod 1 2 NPT connector MAXIMUM MINIMUM Control 125 F 52 C 40 F 40 C Flame Rod Tip 2460 F 1500 F 816 C 40 F 40 C Fireye Terminal Typical Load Maximum Rating 120V 60 Hz 3 or 4 Ind...

Page 3: ...of an overload condition on Terminals 3 4 or 5 To replace the fuse remove power from the system Using a small screwdriver or similar tool remove the fuse from its holder Install a Fireye replacement f...

Page 4: ...tly over the pilot or main burner nozzle WIRING OF FLAME RODS For proper operation of flame rectification systems it is necessary to maintain at least 20 megohms insulating resistance in the flame rec...

Page 5: ...could result in an unsafe condition hazardous to life and property PROGRAMMER JUMPER SETTINGS The M4RT1 has a series of 8 jumpers that are used to configure the Purge timing Pilot Trial for Igni tion...

Page 6: ...is energized APPLICATION AND FUNCTION The M4RT1 provides prepurge ignition and flame safeguard for heating and process gas fired burn ers The recycle or non recycle operation is determined by the 8 ju...

Page 7: ...ers Recycle Operation With jumper 8 in the recycle position the typical wiring arrangement illustrated on pages 10 and 11 for direct spark ignited burners provides the following function 1 With power...

Page 8: ...eading between 4 and 10 micro amps Flame Signal Testing 1 Manually shut off the main fuel valve for a pilot ignited burner or the secondary fuel valve for a direct spark ignited burner 2 Set the test...

Page 9: ...e installation Realign the flame detector so that pilot flame detection requires a larger pilot flame Repeat this test until the main flame lights reliably with minimum pilot WARNING The minimum pilot...

Page 10: ...T SWITCHES OPERATING CONTROL FUEL INTERLOCKS 7 BURNER MOTOR OR CONTACTOR 8 2 A 6 LOCKOUT ALARM KB KA AIR FLOW SWITCH ELECTRONIC CIRCUIT KL KF S1 S2 3 5 4 FLAME AMPLIFIER KL 1 KF 1 KF 2 PILOT MAIN SPAR...

Page 11: ...BURNER FIRES S2 3 5 4 IGNITION 7 8 2 A 6 PILOT S1 B MULTIPLE BURNER SYSTEMS S2 3 5 4 IGNITION 7 8 2 A 6 PILOT S1 LIMIT R MANUAL RESET MAIN GAS VALVE ALARM S P D T RA ALARM SILENCE SWITCH G R STOP STAR...

Page 12: ...h is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AN...

Reviews: