Fireye M4RT1 Manual Download Page 6

6

Pilot Trial for Ignition

Jumpers JP6 and JP7 are used by the factory only to select the PTFI for the M4RT1.  The available
PTFI timing selections are 5 and 10 seconds. The factory set, default PTFI time is 10 seconds (JP6
installed, JP7 not installed).  The PTFI time may only be set by the factory. 

Recycle/Non-recycle Operation

Jumper JP8 is used to select either Recycle or Non-Recycle operation of the M4RT1.  The factory
set, default is Recycle operation (JP8 installed).  To select Non-Recycle operation, cut jumper JP8. 

LED INDICATOR LIGHTS

The M4RT1 has 5 LED lights to indicate the operating status of the control. The function of these
lights are:

Opr Ctrl (Operating Control): 

This LED is lighted whenever input terminal 7 is energized. The

burner system safety interlocks and operating control should be wired in series and connected to the
M4RT1 terminal 7.

Air Flow: 

This LED is lighted whenever all of these conditions exist:

— Input terminal 7 is energized (operating control and safety interlocks closed).

— Input terminal 6 is energized (proof of airflow switch is closed).

— Output terminal 8 is energized (blower motor).

PTFI: 

This LED is energized only during the Pilot Trial For Ignition Period.

Flame: 

This LED is lighted whenever an adequate flame signal is detected between the M4RT1 

terminals S1 & S2. 

Alarm:

 This LED is energized whenever a safety lockout occurs. (See APPLICATION AND 

FUNCTION section).

NOTE: The M4RT1 is not powered until the user’s operating control is energized.

APPLICATION AND FUNCTION 

The M4RT1 provides prepurge, ignition and flame safeguard for heating and process gas fired burn-
ers. The “recycle” or “non-recycle” operation is determined by the #8 jumper on the top PCB. Purge
timing, as well as trial for ignition timing is also set by the jumpers. See JUMPER SETTINGS on
page 5.

The M4RT1 amplifier circuitry is designed to utilize a flame rod for flame detection. The Flame Fail-
ure Response Time (F.F.R.T.) is fixed at 3 seconds. 

Pilot Ignited Burners - “Recycle” Operation

With jumper #8 in the “recycle” position, the typical wiring arrangement illustrated on page 10 for
pilot ignited burners provides the following function:

1.

With power applied to Terminal 7 (Opr Ctrl LED lighted), the burner motor circuit (Terminal 8)
is energized. The control then waits for the proof of airflow input (Terminal 6) to be energized

2.

The Pre-Purge timing starts when terminal 6 is energized.

3.

Following the prepurge period (as determined by jumpers #1 through #5), KL-1 closes, ener-
gizing Terminal 3 which powers the pilot gas valve and Terminal 4 which powers the spark igni-
tion. A five or ten sec. (as determined by jumpers #6 or #7) trial for ignition is initiated (

PTFI

LED lit).

4.

When pilot flame is detected (

Flame 

LED lit), KF-1 closes, energizing Terminal 5 which powers

the main fuel valve, KF-2 opens de-energizing Terminal 4 which shuts off the spark ignition.

5.

When the operating control opens its circuit, or if a power failure occurs, the entire system is de-
energized. Power interruptions in the millisecond range do not affect the operation of the con-
trol. Power interruptions of longer duration will cause the control to recycle.

Summary of Contents for M4RT1

Page 1: ...e Failure Response Time F F R T is fixed at three seconds LED indicator lights indicate the operat ing status of the control In the event of ignition failure or following a safety shutdown the unit lo...

Page 2: ...D1 1000K8 24 inch flame rod 1 2 NPT connector MAXIMUM MINIMUM Control 125 F 52 C 40 F 40 C Flame Rod Tip 2460 F 1500 F 816 C 40 F 40 C Fireye Terminal Typical Load Maximum Rating 120V 60 Hz 3 or 4 Ind...

Page 3: ...of an overload condition on Terminals 3 4 or 5 To replace the fuse remove power from the system Using a small screwdriver or similar tool remove the fuse from its holder Install a Fireye replacement f...

Page 4: ...tly over the pilot or main burner nozzle WIRING OF FLAME RODS For proper operation of flame rectification systems it is necessary to maintain at least 20 megohms insulating resistance in the flame rec...

Page 5: ...could result in an unsafe condition hazardous to life and property PROGRAMMER JUMPER SETTINGS The M4RT1 has a series of 8 jumpers that are used to configure the Purge timing Pilot Trial for Igni tion...

Page 6: ...is energized APPLICATION AND FUNCTION The M4RT1 provides prepurge ignition and flame safeguard for heating and process gas fired burn ers The recycle or non recycle operation is determined by the 8 ju...

Page 7: ...ers Recycle Operation With jumper 8 in the recycle position the typical wiring arrangement illustrated on pages 10 and 11 for direct spark ignited burners provides the following function 1 With power...

Page 8: ...eading between 4 and 10 micro amps Flame Signal Testing 1 Manually shut off the main fuel valve for a pilot ignited burner or the secondary fuel valve for a direct spark ignited burner 2 Set the test...

Page 9: ...e installation Realign the flame detector so that pilot flame detection requires a larger pilot flame Repeat this test until the main flame lights reliably with minimum pilot WARNING The minimum pilot...

Page 10: ...T SWITCHES OPERATING CONTROL FUEL INTERLOCKS 7 BURNER MOTOR OR CONTACTOR 8 2 A 6 LOCKOUT ALARM KB KA AIR FLOW SWITCH ELECTRONIC CIRCUIT KL KF S1 S2 3 5 4 FLAME AMPLIFIER KL 1 KF 1 KF 2 PILOT MAIN SPAR...

Page 11: ...BURNER FIRES S2 3 5 4 IGNITION 7 8 2 A 6 PILOT S1 B MULTIPLE BURNER SYSTEMS S2 3 5 4 IGNITION 7 8 2 A 6 PILOT S1 LIMIT R MANUAL RESET MAIN GAS VALVE ALARM S P D T RA ALARM SILENCE SWITCH G R STOP STAR...

Page 12: ...h is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AN...

Reviews: