9
WIRING DIAGRAM
The wiring base for the DIN rail mount flame modules (60-2537) provides 16 terminals for wiring
the FlameWorx modules.
FIGURE 4.
Internal/External Wiring Connections
FIGURE 5.
Scanner wiring diagram for MBHPS-100D and MBLPS-100D power supply and MBUV-100D,
MBUVS-100D, MBFR-100D, and MBIR-100D FlameWorx modules and their associated scanners.
1
Power for flame rod and UV scanner(s) (from MBHPS-100D, -200D power supply)
2
Power for flame rod and UV scanner (s) (from MBHPS-100D, -200D power supply)
3
Scanner input (flame signal) - Flame Switch (Channel #1)
4
Scanner input (flame signal) - Flame Switch (Channel #1)
5
Scanner input (flame signal)- Flame Switch (Channel #2)
6
Scanner input (flame signal)- Flame Switch (Channel #2)
7
Flame relay normally open (NO) contact - Flame Switch (Channel #1)
8
Flame relay common - Flame Switch (Channel #1)
9
Flame relay normally closed (NC) contact or 4-20 mA output
- Flame Switch (Channel #1)
10
Flame relay normally closed (NC) contact or 4-20 mA output
- Flame Switch (Channel #2)
11
Flame relay common - Flame Switch (Channel #2)
12
Flame relay normally open (NO) contact - Flame Switch (Channel #2)
13
Input power (24 VAC / 24 VDC)
14
Input power common
15
LonWorks Communications (Data A)
16
LonWorks Communications (Data B)
4-20MA
4-20MA
1
3
1
3
2
2
JP4
JP5
INTERNAL CONNECTIONS
EXTERNAL CONNECTIONS
Jumpers JP4 and JP5 are
shipped from the factory
in positions 2-3, providing the flame
relay normally closed (NC)
contact.
USE TERMINAL 14 (INPUT POWER COMMON) AS THE COMMON RETURN FOR
EITHER /BOTH 4-20 mA OUTPUT SIGNALS. JUMPER(S) JP4/JP5 ARE SET IN POSITION 1-2.
69ND1
45CM1
69ND1
45CM1
48PT2
48PT2
UV1A
UV1A
1
2
3
4
5
6
13
14
45UV5-1008
45UV5-1009
1
2
3
4
5
6
13
14
1
2
3
4
5
6
13
14
1
2
3
4
5
6
13
14
45UV5-1008
45UV5-1009
1
2
4
5
7
8
10
L1
L2
MBHPS-100D
MBUVS-100D
MBFR-100D
MBIR-100D
CONNECT TO TERMINALS
10 AND 11 ON MBHPS/MBLPS
POWER SUPPLY OR SUITABLE
120VAC POWER SOURCE
CHANNEL 2
BLACK LEADS
BLACK LEADS
CHANNEL 2
CHANNEL 2
CHANNEL 2
CHANNEL 1
CHANNEL 1
CHANNEL 1
ALL DIN RAIL FLAMEWORX
MODULES USE THE 60-2537
WIRING BASE.
NOTE: TERMINALS 1 AND 2 OF THE
MBIR-100D FLAMEWORX MODULE
DO NOT HAVE TO BE POWERED BY
MBHPS-100D POWER SUPPLY.
MBLPS-100D AND MBHPS-100D
USE THE 60-2538 WIRING BASE.
MBUV-100D
CHANNEL 1
REPLACEMENT FUSE
FOR MBPS-100D
(P/N 23-184).
RED LEADS
RED LEADS
11
12
3
4
5
6
10
11
12
EARTH
MBLPS-100D
(120 VAC)
PHOTOCELL OR
FLAME ROD ONLY
MBFR ONLY
6
5
4
3
Summary of Contents for FlameWorx MBFR-100D