WIRING DIAGRAM

 

The wiring base for the DIN rail mount flame modules (60-2537) provides 16 terminals for wiring
the FlameWorx modules.

 

FIGURE 4.

Internal/External Wiring Connections

FIGURE 5.

Scanner wiring diagram for MBHPS-100D and MBLPS-100D power supply and MBUV-100D, 
MBUVS-100D, MBFR-100D, and MBIR-100D FlameWorx modules and their associated scanners.

1

Power for flame rod and UV scanner(s) (from MBHPS-100D, -200D power supply)

2

Power for flame rod and UV scanner (s) (from MBHPS-100D, -200D power supply)

3

Scanner input (flame signal) - Flame Switch (Channel #1)

4

Scanner input (flame signal) - Flame Switch (Channel #1)

5

Scanner input (flame signal)- Flame Switch (Channel #2)

6

Scanner input (flame signal)- Flame Switch (Channel #2)

7

Flame relay normally open (NO) contact - Flame Switch (Channel #1)

8

Flame relay common - Flame Switch (Channel #1)

9

Flame relay normally closed (NC) contact or 4-20 mA output 
- Flame Switch (Channel #1)

10

Flame relay normally closed (NC) contact or 4-20 mA output 
 - Flame Switch (Channel #2)

11

Flame relay common - Flame Switch (Channel #2)

12

Flame relay normally open (NO) contact - Flame Switch (Channel #2)

13

Input power (24 VAC / 24 VDC)

14

Input power common

15

LonWorks Communications (Data A)

16

LonWorks Communications (Data B)

4-20MA

4-20MA

1

3

1

3

2

2

JP4

JP5

INTERNAL CONNECTIONS

EXTERNAL CONNECTIONS

Jumpers JP4 and JP5 are
shipped from the factory
in positions 2-3, providing the flame
relay normally closed (NC)
contact.

USE TERMINAL 14 (INPUT POWER COMMON) AS THE COMMON RETURN FOR
EITHER /BOTH 4-20 mA OUTPUT SIGNALS. JUMPER(S) JP4/JP5 ARE SET IN POSITION 1-2.

69ND1
45CM1

69ND1
45CM1

48PT2

48PT2

UV1A

UV1A

1
2
3
4
5
6

13
14

45UV5-1008
45UV5-1009

1
2
3
4
5
6

13
14

1
2
3
4
5
6

13
14

1
2
3
4
5
6

13
14

45UV5-1008
45UV5-1009

1
2
4
5
7
8

10

L1

L2

MBHPS-100D

MBUVS-100D

MBFR-100D

MBIR-100D

CONNECT TO TERMINALS

10 AND 11 ON MBHPS/MBLPS

POWER SUPPLY OR SUITABLE 

120VAC POWER SOURCE

CHANNEL 2

BLACK LEADS

BLACK LEADS

CHANNEL 2

CHANNEL 2

CHANNEL 2

CHANNEL 1

CHANNEL 1

CHANNEL 1

ALL DIN RAIL FLAMEWORX
MODULES USE THE 60-2537
WIRING BASE.

NOTE: TERMINALS 1 AND 2 OF THE
MBIR-100D FLAMEWORX MODULE
DO NOT HAVE TO BE POWERED BY 
MBHPS-100D POWER SUPPLY.

MBLPS-100D AND MBHPS-100D 
USE THE 60-2538 WIRING BASE.

MBUV-100D

CHANNEL 1

REPLACEMENT FUSE
FOR MBPS-100D 
(P/N 23-184).

RED LEADS

RED LEADS

11
12

3
4
5
6

10
11
12

EARTH

MBLPS-100D

(120 VAC)

PHOTOCELL OR 
FLAME ROD ONLY

MBFR ONLY

6

5

4

3

Summary of Contents for FlameWorx MBFR-100D

Page 1: ...selected via dipswitch Fireye FlameWorx modules can be used in a number of flame detection applications In addition the modules also incorporate LonWorks communications which allow the use of Fireye programming modules e g multi burner module which provide safe start check purge timing safety lockout etc which further expands on the functionality of the flame switches LonWorks communications use a...

Page 2: ...up to 12 modules Flame Scanners UV1A3 Ultra violet scanner for use with MBUV modules 1 2 NPT mount 3 flex conduit UV1A6 Ultra violet scanner for use with MBUV modules 1 2 NPT mount 6 flex conduit UV2 Ultra violet scanner for use with MBUV modules 3 8 NPT mount 3 flex conduit UV8A Ultra violet scanner for use with MBUV modules 1 2 NPT mount 90 head 6 cable no conduit 45UV3 1050 Ultra violet scanner...

Page 3: ...OWER SUPPLIES Input Supply Voltage MBLPS 100D 120 VAC 10 15 50 60 Hz MBHPS 100D 120 VAC 10 15 50 60 Hz MBLPS 200D 230 VAC 10 15 50 60 Hz MBHPS 200D 230 VAC 10 15 50 60 Hz Maximum current output MBLPS 100D 200D 1 4A 24 VDC Will power up to 10 FlameWorx modules MBHPS 100D 200D 25mA 600 VAC Will power up to 20 flame scanners UV and or flame rod FLAMEWORX MODULES and POWER SUPPLIES Operating Temperatu...

Page 4: ...ER RLY 1 RLY2 SIG 1 CS1 COM CS2 MBUVS 100D SIG 2 1 4 1 1 38 1 06 2 VIEW A A P N 60 2538 FLAMEWORX MODULES AND POWER SUPPLY MODULES HAVE IDENTICAL DIMENSIONS DIN RAIL MOUNT 60 2539 12 60 2539 24 60 2539 36 L 12 305 L 24 610 L 36 914 PART NO LENGTH L 59 VIEW A A P N 60 2537 35 3 7 5 25 36 5 15 59 15 15 59 15 27 DIMENSIONS IN INCHES MM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12...

Page 5: ...blink in the manner described below to indicate the following fault conditions Fault Condition Corrective Action CPU failure Replace FlameWorx module Communication failure Check communication wiring Check communication master Press CS1 and CS2 communication push buttons Set dipswitch 6 to On position for stand alone module Shutter check failure on Check shutter operation on scanner Channel 1 Check...

Page 6: ...alone mode the FlameWorx module will not attempt to communicate on a communications network The settings for dipswitches 1 through 5 are inhibited when set for stand alone mode When the FlameWorx modules are used in a communication network e g Fireye MB Module dipswitch 6 must be set in the Network mode to enable communications Also refer to Communica tion Pushbuttons CS1 and CS2 Dipswitch 6 Off S...

Page 7: ... proportional to flame signal strength for each flame switch via test jack points located on the face plate of the mod ule In addition to these analog outputs via the test jacks jumpers JP4 and JP5 will provide an additional 4 20 mA flame signal via terminals on the connector of the FlameWorx module to allow an easier means of wiring to a remote meter Use terminal 14 Input power common as the com ...

Page 8: ...snaps into place To mount the flame switch module or power supply onto the wiring base 1 Align the flame switch module with its wiring base and insert the edge of the flame switch mod ule into the connector on the wiring base 2 Using a medium slotted screw driver with a 4 inch shaft minimum tighten down the two retaining screws on the flame switch module To remove the wiring base from the DIN moun...

Page 9: ...tch Channel 2 13 Input power 24 VAC 24 VDC 14 Input power common 15 LonWorks Communications Data A 16 LonWorks Communications Data B 4 20MA 4 20MA 1 3 1 3 2 2 JP4 JP5 INTERNAL CONNECTIONS EXTERNAL CONNECTIONS Jumpers JP4 and JP5 are shipped from the factory in positions 2 3 providing the flame relay normally closed NC contact USE TERMINAL 14 INPUT POWER COMMON AS THE COMMON RETURN FOR EITHER BOTH ...

Page 10: ...0D MBFR 100D MBIR 100D CONNECT TO TERMINALS 10 AND 11 ON MBHPS MBLPS POWER SUPPLY OR SUITABLE 230VAC POWER SOURCE CHANNEL 2 BLACK LEADS BLACK LEADS CHANNEL 2 CHANNEL 2 CHANNEL 2 CHANNEL 1 CHANNEL 1 CHANNEL 1 ALL DIN RAIL FLAMEWORX MODULES USE THE 60 2537 WIRING BASE NOTE TERMINALS 1 AND 2 OF THE MBIR 100D FLAMEWORX MODULE DO NOT HAVE TO BE POWERED BY MBHPS 200D POWER SUPPLY MBLPS 200D AND MBHPS 20...

Page 11: ...11 ...

Page 12: ...h is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product ...

Reviews: