Wiring Base P/N
For use with
60-2537
MBUV-100D, MBUVS-100D, MBIR-100D, and MBFR-100D
60-2538
MBHPS-100D, -200D and MBLPS-100D, -200D.
The 60-2537 wiring base for the flame switch modules provides a sixteen (16) screw connector ter-
minal strip that will accept 22 to 14 AWG (0.5 - 1.5 mm
2
) wire.
The 60-2538 wiring base for the low and high style power supplies provide a twelve (12) screw con-
nector terminal strip that will accept 22 to 14 AWG (0.5 - 1.5 mm
2
) wire.
INSTALLATION OF DIN RAIL MOUNT FLAME SWITCH MODULES AND POWER SUPPLIES
The wiring bases for the flame switch module (60-2537) and high and low voltage power supplies
(60-2538) mount onto the DIN mounting rails (60-2539-12, -24, -36). The flame switch module and/
or power supplies are then screwed onto their respective wiring base.
To mount the wiring base onto the DIN mounting rail
1.
Position the bottom edge of the DIN mounting rail into the slot on the bottom of the wiring base
(60-2537 or 60-2538).
2.
Insert a small screw driver into the slot of the white plastic retainer on the top rear section of the
wiring base.
3.
Lift up the white plastic retainer and press the upper half of the wiring base against the DIN
mounting rail until it snaps into place.
To mount the flame switch module or power supply onto the wiring base.
1.
Align the flame switch module with its wiring base and insert the edge of the flame switch mod-
ule into the connector on the wiring base.
2.
Using a medium slotted screw driver with a 4-inch shaft (minimum), tighten down the two
retaining screws on the flame switch module.
To remove the wiring base from the DIN mounting rail.
1.
Insert a small screwdriver into the slot of the white plastic retainer on the top rear section of the
wiring base.
2.
Lift up the white plastic retainer and pull the flame switch module/wiring base forward.
3.
Slide the bottom of the wiring base off of the DIN mounting rail.
Connections for MBHPS-100D, -200D Power Supply
TERMINAL
FUNCTION
1, 7
Power for UV scanners (UV1A, 45UV5). Connect to terminals 1
and 2 of MBUV-100D and MBUVS-100D.
2, 4
Power for flame rods and photocells. Connect to terminals 1 and 2
of MBFR-100D.
10
Incoming line power - L1 (120 VAC for MBHPS-100D, 230 VAC
for MBHPS-200D).
11
Incoming line power common - L2.
12
Earth Ground.
Connections for MBLPS-100D, -200D Power Supply
3, 4
24 VDC Power for FlameWorx modules. Connect to terminal 13
of FlameWorx modules.
5, 6
24 VDC common for FlameWorx modules. Connect to terminal
14 of FlameWorx modules.
10
Incoming line power - L1 (120 VAC for MBLPS-100D, 230 VAC
for MBLPS-200D).
11
Incoming line power common - L2.
12
Earth Ground.