3
PRODUCT SPECIFICATIONS
FLAMEWORX MODULES
Supply Voltage:
24 VAC +10 / -15%, 50 / 60 Hz @ 100 mA.
24 VDC +10 / -15%, @ 100 mA.
Power Consumption:
2.4 VA (100 mA)
Flame Relay Contacts: (1 Form C SPDT for each flame switch, 2 per module.)
5 amps (resistive load) @ 250 VAC
3 amps (resistive load) @ 24 VDC
250 VA (maximum connected load) each
40 mA (minimum connected load current).
Contact Material:
Silver cadmium oxide
Flame Signal Output:
4-20 mA (current source). Max connected load: 750 ohms.
POWER SUPPLIES
Input Supply Voltage:
MBLPS-100D:
120 VAC +10 / -15%. 50/60 Hz.
MBHPS-100D:
120 VAC +10 / -15%. 50/60 Hz.
MBLPS-200D:
230 VAC +10 / -15%. 50/60 Hz.
MBHPS-200D:
230 VAC +10 / -15%. 50/60 Hz.
Maximum current output:
MBLPS-100D, -200D:
1.4A @ 24 VDC (Will power up to 10 FlameWorx modules)
MBHPS-100D, -200D:
25mA @ 600 VAC (Will power up to 20 flame scanners -
UV and/or flame rod).
FLAMEWORX MODULES and POWER SUPPLIES
Operating Temperature:
-40
°
F to 140
°
F (-40
°
C to 60
°
C)
Storage Temperature:
-40
°
F to 176
°
F (-40
°
C to 80
°
C)
Humidity:
85
%
RH (max), non-condensing.
Agency Approvals:
Factory Mutual (FM)
Canadian Standards Association (CSA)
Year 2000 Compliant in accordance with BSI document DISC PD2000-I:1998