25
Both the probe and ambient temperatures are displayed and should indicate the entered ambient tem-
perature following calibration.
NOTE: The probe should be at ambient temperature when calibrated.
Draft Zero: The Draft Sensor is standard on the Firetron FT-1200-1 and FT-1300-1. The Draft sen-
sor is pre-calibrated at the factory. This menu option is used where the sensor requires re-calibration.
Draft Zero is a measure of ambient air pressure, with an output displayed in Volts. For details on how
to complete a Draft calibration refer to Section 6.6, Calibrating the Draft Sensor.
Draft Span: The Draft Sensor is standard on the Firetron 1000 Series. A Draft Span calibration
involves the use of a monometer and squeeze bulb. Refer to Section 6.6, Calibrating the Draft Sensor.
A differential pressure reading will be made (FT1200-1, FT1300-1 only).
EXIT
F1
F2
F3
F4
HELP
USE CURSOR KEYS TO ENTER CURRENT
AMBIENT XXC
AMBIENT TEMPURATE.
PRESS "ENTER" WHEN READY TO CAL
EXIT
F1
F2
F3
F4
HELP
CAL
PRESS ’CAL’ TO CALIBRATE
PROBE: XXX.XXX°C
AMBIENT: XXX.XXX°C
EXIT
F1
F2
F3
F4
HELP
CONNECT PROBE...
PRESS ’ENTER’’ WHEN READY TO CAL.
EXIT
F1
F2
F3
F4
HELP
CAL
PRESS ’CAL’ TO CALIBRATE
DRAFT ZERO 0.90V
EXIT
F1
F2
F3
F4
HELP
PRESS "ENTER" WHEN READY TO CALIBRATE
PRESSURE XX.X wgc