background image

6

4.

Mount scanner sight pipe by either:

— Centering a Fireye No. 60-1664-3 (NPT) or 60-1664-4 (BSP) swivel mount over the hole

and installing the sight pipe on the swivel mount, 

or 

— Inserting the end of the sight pipe into the hole, aligning the pipe to the desired viewing

angle and tack weld. (Welding must be adequate to temporarily support the weight of the
installed scanner). The sight pipe should be arranged to slant downward so that the dirt and
dust will not collect in it.

FIGURE 5.

5.

When a satisfactory sighting position has been confirmed by operational test, (see section on
alignment), the sight pipe should either be firmly welded in place or, if the swivel mount is used,
the base position should be secured by tightening the three hex head cap screw located on the
swivel mount ring. In certain older style swivel mounts, tack welding may be required.

6.

Excessive flame signal can affect flame discrimination and prevent the control connected to the
scanner from performing properly. To reduce the signal level of the tube, or improve flame dis-
crimination, orifices may be installed to decrease the scanner’s field of view and reduce its sen-
sitivity. Installation of the orifice disk is shown in Figure 11.

7.

The scanner viewing window must be kept free of contaminants (oil, smoke, soot, dirt) and the
scanner temperature must not exceed its maximum rating. Both requirements will be satisfied by
continuous injection of purge air.

The scanner mounting may be made with provision for purge air through the 3/4” opening as shown
in Figure 6, Item A or C, or through a 1" tee/wye connection as shown in Figure 6, Item B. Normally
only one of the two connections is provided with purge air and the other is plugged. When a Fireye
coupling is used as shown in Figure 6, the 1" tee/wye connection is used for the purge air (plug 3/4”
opening).

Under normal temperature conditions, with clean burning fuels and moderate ambient temperature
conditions, purge air flow of approximately 4 SCFM (113 L/min) is generally adequate. A 0.1 psig
positive pressure difference between the atmosphere and boiler pressure measured at right angle to
the purge air flow, should result in a purge air flow of 4 SCFM. Up to 15 SCFM (425 L/min) may be
required for fuels that may produce high levels of smoke of soot or for hot environments to maintain
scanner internal temperature within specifications.

NOTE: The maximum viewing field of the lens is one inch per foot. Do not use more than one foot of
one inch sight pipe. Increase sight pipe diameter one inch for every additional foot of sight pipe
length used, to avoid restricting the scanner’s field of view. Temperature in the scanner housing
should not exceed those temperature limits listed in the specifications. Excessive temperatures will
shorten scanner life.

BUT THIS

NOT THIS

NOT THIS

FLAME MUST COMPLETELY COVER SIGHT OPENING

WARNING: Sighting position of the flame scanner should insure that the scanner does not
respond to the ignition spark.

Summary of Contents for 65UV5-1000

Page 1: ...ed to terminate the cable at the housing Note The 65UV5 1000 1000E scanners became obsolete in 2008 and were replaced by the enhanced capability of the 65UV5 1004 and 1004E scanners APPLICATION Fireye...

Page 2: ...the ultraviolet tube While the shutter is open flame presence or absence is detected The self check shutter operation and fault diagnostics are fully described later in this bulletin SPECIFICATIONS FI...

Page 3: ...se with dirty dusty fuels may require up to 15 SCFM 425 l min Pressure Adequate to overcome furnace or windbox pressure Temperature Rating 40 F to 150 F 40 C to 65 C Humidity 0 to 95 relative humidity...

Page 4: ...ressure Temperature Rating 40 F to 150 F 40 C to 65 C maximum dependent on T classification Humidity 0 to 95 relative humidity non condensing ELECTRICAL Input Power 24 Vdc 20 25 supply current 100 mA...

Page 5: ...ame too short or in the wrong position to ignite the main flame reliably thus prohibiting main fuel admission NOTE Reliable signals must be obtained at all air flows and furnace loads ranges of fuel f...

Page 6: ...atisfied by continuous injection of purge air The scanner mounting may be made with provision for purge air through the 3 4 opening as shown in Figure 6 Item A or C or through a 1 tee wye connection a...

Page 7: ...HT PIPE BY OTHERS ALTERNATE MOUNTING NOT ADJUSTABLE 60 1664 1 SWIVEL MOUNT 35 127 HEAT INSULATING NIPPLE 60 1199 1 NPT 60 1199 2 BSP SEALING COUPLING WITH QUARTZ WINDOW REQUIRED WHEN SCANNER LENS IS E...

Page 8: ...N NOTE 4 FLAME OFF FLAME ON NOTE5 NOTE 6 FLAME STRENGTH EARTH GROUND EXTERNAL FUSE CABLE COLOR CODES AND DESCRIPTIONS BLUE Relay voltage input 5 VDC to 230 VAC 1 mA to 2000 mA fused BLACK Safety Relay...

Page 9: ...The installer must use a suitable EX cable gland or conduit fitting at the CEX housing s NPT threaded cable entry opening To reduce electrical noise interference take precautions to keep the scanner...

Page 10: ...sed can vary between 50 ms and 300 ms In the event of a self check failure the flame relay will de energize INDICATION LEDs The 65UV5 contains a color coded internal LED that indicates flame status an...

Page 11: ...the ignition spark This is accomplished by cut ting off the fuel to the pilot and attempting to start the pilot using the spark igniter If the system responds to the spark the sighting should be real...

Page 12: ...front is a plane within the combustion space separating the region of unburned fuel from the burning fuel Note There is an inverse relationship between discrimination and sensitivity Table 4 Heat Insu...

Page 13: ...e tube can only be inserted into the socket with the electrodes broadside to the shutter window 4 Clean the quartz lens and tube with glass detergent or glass cleaning agents which contain no abrasive...

Page 14: ...r Description 4 290 1 UV Tube 61 6974 Shutter Assembly 002608 001 Flange Gasket 002611 001 Scanner Lens 101537 001 Lens Retaining Ring 107427 006 Lens O Ring 2 required UV TUBE SHUTTER SECURING SCREWS...

Page 15: ...127 1 NPT HEAT INSULATING NIPPLE 35 127 3 BSP HEAT INSULATING NIPPLE L 92 48 QUARTZ WINDOW for 61 1199 Sealing Coupling shown in Fig 15 A 60 1664 3 NPT SWIVEL MOUNT 60 1664 4 BSP SWIVEL MOUNT A B B 60...

Page 16: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Reviews: