9
®
Note: When the older generations of 65UV5-1000 or -1000E scanners are used for a Class 1, Div. 2
application, the cable gland MUST be removed and replaced with P/N 129-149, liquid tight cable
gland, so that liquid tight flexible conduit (Anaconda Sealtight ® 1/2" Type H.T.V.A or equivalent,
available at any electrical supply outlet) can be inserted over the existing cable. The newer genera-
tion 65UV5-1004 and 1004E utilize a special cable that is approved for use in a Class 1, Div. 2 area
without the use of the flexible conduit.
SCANNER WIRING - CEX VERSIONS
CEX models contain two internal four-pole terminal blocks for the user to connect their scanner
cable. The terminal blocks are identified by the internal wire color code and functions as described in
Table 2 and Figure 9 below.
The installer must use a suitable EX cable gland or conduit fitting at the CEX housing's ¾" NPT
threaded cable entry opening.
To reduce electrical noise interference, take precautions to keep the scanner cable away from any
high inductive wiring associated with high inductive loads or high voltage, high energy spark igni-
tion systems.
Table 2:
WIRING OF SIMPLICITY MODEL 65UV5-1004 “CEX” SCANNERS
Note: 4-20mA negative connection should connect to the power supply negative wire (white).
TERMINAL
INTERNAL WIRE
COLOR CODE
FUNCTION
TERMINAL BLOCK 1
( RELAY CONTACT CONNECTIONS)
1
RED
FLAME RELAY (N.C.)
2
BLACK
FAULT/ FLAME RELAY (COM)
3
BLUE
FAULT RELAY (N.O.)
4
YELLOW
FLAME RELAY (N.O.)
TERMINAL BLOCK 2
(POWER CONNECTIONS)
5
WHITE
24 VDC (-) SUPPLY
6
BROWN
24 VDC (+) SUPPLY
7
GREEN
EARTH GROUND
8
ORANGE
4-20 mA OUTPUT (+)
ALTERNATE LIQUID
TIGHT CONNECTION
WARNING: Unit should be electrically protected by external fuses (see Fig. 7 and Fig. 8 for
rating) to prevent damage to unit in case of a short or overload.