Fig.15:
Power Supply Connections
7.7 POWER SUPPLY CONNECTIONS
The power supply is part of the Main Fire Alarm Module and the Chassis. The ratings are:
Model
FW-C2Z, FW-C4Z
:
Electrical input ratings:
120 VAC, 60 Hz, 2.0A (Uses 3A in line time delay fuse)
Power supply total current:
2.75 A maximum
Battery Fuse on Main Module:
F1:
Replace with 10 Amp, 1-1/4" Fast Acting Fuse
Model
FW-C4EZ
:
Electrical input ratings:
120 VAC, 60 Hz, 2.5A (Uses a 4.0A circuit breaker)
Power supply total current:
6 A maximum
Battery Fuse on Main Module:
F1:
Replace with 10 Amp, 1-1/4" Fast Acting Fuse
CAUTION:
Do not exceed power supply ratings.
See appendix "C" for specifications. Wire as shown using proper wire gauges.