3.1 MODELS
Model:
FW-C2Z
Small enclosure Fire Alarm Control Panel with two Class B (Style B) or one Class A (Style D) Initiating Circuits,
and 2 Power Limited Class A/B (Style Z/Y) Notification Circuits (1.70 amperes each, 2.4 amperes total) with
individual trouble indicators. Common Alarm & Trouble Relays. Interface for Remote Trouble Indicator.
Resettable Four Wire Smoke Detector Power Supply. May have one of FW-DACT, FW-RPM, FW-RB4, or
FW-RB8 installed. Can be used with 4 amp-hour or 6.5 amp-hour batteries (2 required).
Model:
FW-C4Z
Small enclosure Fire Alarm Control Panel with four Class B (Style B) or two Class A (Style D) Initiating
Circuits, and 2 Power Limited Class A/B (Style Z/Y) Notification Circuits (1.70 amperes each, 2.4 amperes
total) with individual trouble indicators. Common Alarm & Trouble Relays. Interface for Remote Trouble
Indicator and/or 1 to 3 of FW-RB8 Remote Multiplex Annunciators. Resettable Four Wire Smoke Detector
Power Supply. May have one of FW-DACT, FW-RPM, FW-RB4, or FW-RB8 installed. Can be used with 4
amp-hour or 6.5 amp-hour batteries (2 required).
Model:
FW-C4EZ
Large enclosure Fire Alarm Control Panel with four Class B (Style B) or two Class A (Style D) Initiating
Circuits, and 2 Power Limited Class A/B (Style Z/Y) Notification Circuits (1.70 amperes each, 5 amperes total)
with individual trouble indicators. Common Alarm & Trouble Relays. Interface for Remote Trouble Indicator
and/or 1 to 3 of FW-RB8 Remote Multiplex Annunciators. Resettable Four Wire Smoke Detector Power
Supply. May have one of FW-DACT or FW-RPM, and one FW-EZM4 installed. May also have one of FW-RB4
or FW-RB8 installed. Can be used with 4 amp-hour, 6.5 amp-hour, or 10 amp-hour batteries (2 required).
Model:
FW-EZM4
Zone Expansion Module for the FW-C4EZ. Brings the total capacity to eight Class B (Style B) or four Class
A (Style D) Initiating Circuits, and 4 Power Limited Class A/B (Style Z/Y) Notification Circuits (up to 1.7
amperes each, 5 amperes total).
Model:
FW-RB8
Relay Module for the FW-C4Z or FW-C4EZ. Adds eight configurable Form-C Relays rated 1A, 28 VDC.
Model:
FW-RB4
Relay Module for the FW-C4Z or FW-C4EZ. Adds four configurable Form-C Relays rated 1A, 28 VDC.
Model:
FW-DACT
Digital Communicator / Dialer Module.
Model:
FW-RPM
City Tie / Reverse Polarity Module.
Model:
CH-429
Accessory Mounting Plate for the FW-C2Z, or FW-C4Z if one of FW-RB4, FW-RB8, FW-RPM, or FW-DACT
Modules are to be used.
3.2 ACCESSORIES
Model:
FW-RA-LED
8 Zone Remote Annunciator (ULC and UL Approved)
Model:
FW-RTI
Remote Trouble Indicator (ULC and UL Approved)