MAIN FIRE ALARM BOARD
FIELD WIRING TERMINALS
P6
F1
10 AMP
BATTERY
FUSE
SW13
1
2
3
JW2
P3
2
3
1
BATT+
P4
P5
P2
BATT-
XMFR
XMFR
JW1
P7
P8
JW4
JW5
JW3
JW6
SW11
SW9
P1
Page 12 of 36
Fig.5:
Main Fire Alarm Module
6.0 MODULE SETTINGS
6.1 MAIN FIRE ALARM MODULE
Class A / B Selection:
On the FW-C2Z, FW-C4Z and FW-C4EZ only,
JW1 & JW2
are connected from 1 to 2 for Initiating Circuit
Class B
(Style B) operation
, and from 2 to 3 for
Class A (Style D) operation
. JW2 is present on the FW-C2Z.
Note that
the Class A/B selection affects all Initiating Circuits, and must be used with the correct Configuration DIP
Switch Setting.
Zone Adder Module:
On an FW-C4EZ only, remove the jumper on
JW4
if a
FW-EZM4 Zone Expansion
is installed. The Zone Adder
Module is plugged into
P6 & P7
.
Relay Module:
Remove the jumper on
JW3
if an
FW-RB4 or FW-RB8 Relay Module
is installed. The Relay Module is plugged into
P1
.
Digital Communicator:
Remove the jumper on
JW6
if a
FW-DACT Digital Communicator
is installed. The Digital Communicator is plugged
into
P8
.
City Tie:
Remove the jumper on
JW6
if a
FW-RPM City Tie
is installed. The City Tie is plugged into
P8
.
Battery:
Connected to
P2(+’ve) & P3(-’ve)
via the factory installed cables.
Transformer:
Factory wired to
P4 & P5
, do not disconnect.
JW5
There should be no jumper here; do not use.
SW9,11,13
Configuration DIP Switches.
Battery Fuse F1:
Replace with 10 Amp, 1-1/4" Fast Acting Fuse