4
CONSTRUCTION OF ENCLOSURE
WARNING: All fire pits must have a gas shutoff on the outside of the fire
pit to allow for emergency shut off and maintenance.
WARNING: For electronic ignition models, there must be an electrical shut
off (wall switch or breaker) on the exterior of the fire pit or on adjacent wall
to allow for emergency shutdown and maintenance. Verify correct power
supply.
WARNING: Always use proper materials and construction for gas supply,
power and enclosure. Materials must be non-combustible in both initial
installations as well as over time.
WARNING: For electronic ignition models requiring power supply – a
qualified, licensed electrician must install power supply. An outdoor NEMA
rated GFCI Receptacle outlet should be installed on the interior of the
enclosure above grade to supply power to system.
WARNING: The enclosure is recommended to incorporate 1 vent on at
least two opposing sides (2 vents total) at a minimum size of 18 sq. inches
each (Example: 3”x 6” or larger). Installation of the vents in the mid to
lower area of the enclosure is recommended. Ventilation allows for heat
and/or residual fuel to escape. Failure to properly vent enclosure may
result in the fire pit overheating or explosion. Overheating could lead
to heat damage to internal components. Some enclosures may require
more ventilation based on material, size, and extended use. The vent may
serve as a drain as well when installed at bottom sidewall to prevent water
build up. Always consult with local municipality regarding any local code
requirements
WARNING: The interior space of the enclosure surrounding the valve box
cannot be filled with any material (gravel, crushed rock, concrete, etc.).
WARNING: The fire pit assembly should be recessed 4”- 6" from the top
of the enclosure to protect flame from being blown out. Some areas may
require deeper recession.
WARNING: The enclosure must be constructed on a stable surface. The
weight of the fire feature must be supported by the plate or pan and
not by any control/valve box. For electronic ignition models the control/
valve box must be above grade with adequate drainage to prevent water
damage to the controls inside the box. Installer is responsible for ensuring
there is enough space for electronics – see technical drawings provided by
manufacturer. Installer is responsible to ensure that the structure is level.
Blocks, bricks or L-brackets can be used to build a support ledge for the
system plate or pan.
WARNING: It is the responsibility of the installer to provide proper installa-
tion to allow for easy accessibility for service and/or repairs. Installer must
not build capstone inner ledge over outer lip of plates or pans (unless ac-
cess panel door or alternate access is incorporated). Building capstone in-
ner ledge over outer edge of plates or pans will impede access to system
and result in the need to crack capstones to gain access. Warming Trends
is not responsible for damage to enclosure for any reason whatsoever.
GENERAL FIRE PIT INSTALLATION
WARNING: Read all warnings prior to installing your fire feature
WARNING: All gas products should be installed by qualified professionals
that are locally licensed by the authority having jurisdiction in gas piping.
WARNING: We suggest that our products be serviced annually by a
licensed plumber.
WARNING: It is the installer’s responsibility to follow installation instruc-
tions carefully in order to ensure a safe installation, safe operation and safe
ongoing servicing.
WARNING: You must confirm this appliance is built for gas use – Natural
SELECTING A LOCATION FOR YOUR FIRE FEATURE
WARNING: All fire pits, match lit kits, spark ignition, and electronic igni-
tion systems are designed and intended for outdoor use only.
WARNING: For electronic ignition models, there must be an electrical
shut off (wall switch or breaker) on the exterior of the fire pit or on adja-
cent wall to allow for emergency shutdown and maintenance. Distance
may be determined by local code.
WARNING: All fire pits must have a gas shutoff located outside of the fire
pit to allow for emergency shut off and maintenance.
WARNING: Select a location where the fire pit can be attended during
operation. Never leave an operating fire pit unattended or by someone
not familiar with its operation or emergency shut off locations.
WARNING: Both children and adults should be alerted to the hazards
of high surface temperatures and should remain a safe distance away to
avoid burns and clothing ignition.
WARNING: Young children should be carefully supervised when they are
in the area of a fire pit.
WARNING: Clothing or other flammable materials should not be placed
on or near fire pit.
WARNING: Fire pits create very high temperatures - Combustibles must
be located far enough away that there is no risk of ignition.
IMPORTANT: It is recommended that material such as granite, marble or
other dense stone be kept an appropriate distance away from flame due
to risk of cracking. Manufacturer is not responsible for damage to any fire
pit material for any reason.
MATCH LIGHT
Minimum
Maximum
Natural Gas
3.5” W.C.
7.0” W.C.
Liquid Propane
11.0” W.C.
13.0” W.C.
3V - 3VIK
Minimum
Maximum
Natural Gas
4.5” W.C.
10.0” W.C.
Liquid Propane
11.0” W.C.
13.0” W.C.
STANDARD - 24VIKSC
& 24VIKHC
Minimum
Maximum
Natural Gas
3.0” W.C.
5.0” W.C.
Liquid Propane
8.0” W.C.
12.0” W.C.
PREMIUM - P24VIKSC
& P24VIKHC
Minimum
Maximum
Natural Gas
3.5” W.C.
14.0” W.C.
Liquid Propane
8.0” W.C.
14.0” W.C.
WARNING: It is the responsibility of the installer to follow ALL LOCAL
CODES concerning the installation and operation of the fire pit. In the ab-
sence of local codes, please follow:
• Fixed piping system: The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 or International Fuel Gas Code.
• Electrical ground: The National Electrical Code, ANSI/NFPA 70.
WARNING: Only use gas/fuel type specified for this fire pit. See label on the
burner. Verify correct gas/fuel type and pressure. Never use an alternative
fue, included but not limited to biofuel, ethanol, lighter fluid or any other
alternative fuel other than Liquid Propane or Natural Gas.
WARNING: Gas pressure and type should be checked prior to use and
installation.
FIRE PIT CLEARANCES
• 36” horizontally from any structure or combustibles.
• Overhead clearance should be a minimum of 120”.
• Choose a location that allows easy access for installation and
maintenance of the fire pit.
• Pick a location that allows sufficient horizontal room to enjoy the
fire pit while allowing a safe distance from the heat and flame.
• Always consult with local municipality regarding any local code
requirements