26
Finalizing the Installation
(for qualified installers only)
© Travis Industries
4/23/2021 - 1552
564 GSR2 35K CF
Minimum Vent Configuration
Use 5x8” Diameter Coaxial Vent
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
One elbow (30° or 45°) may be used on the horizontal run.
HINT
: Use minimum vent kit “H” (96200332) from Travis Ind. (additional vent may be required).
0 feet
0 feet
0
fe
et
0
fe
e
t
Exhaust Restrictor - Remove (stock)
Exhaust Restrictor - Remove (stock)
Diffuser #1 (stock)
Diffuser #1 (stock)
Intake Restrictor #1 (stock)
Intake Restrictor #1 (stock)
5
fe
e
t (
1.
5
m
)
5
fe
et
(
1.
5
m
)
10
fe
et
(
3.
0
m
)
10
fe
et
(3
.0
m
)
Max. 10' (3048mm) Horizontal Section(s)
Max. 10' (3048mm) Horizontal Section(s)
Min. 3.9" (100mm) Horizontal Section
Min. 3.9" (100mm) Horizontal Section
5 feet (1.5 m)
5 feet (1.5 m)
1' (305mm) Vertical Section Attached Directly to Fireplace
2' (610mm) Vertical Section Attached Directly to Fireplace
NG (Natural Gas)
LP (Propane)