44 Installation
(for qualified installers only)
© Travis Industries
8/25/2017 - 1450
42 Apex CF
Facing Requirements
The fireplace requires non-combustible facing (typically 1/2" thick concrete-board) from the base of
the fireplace to the framing header (min. 78-1/2””). The non-combustible facing must extend to the
framing members on both sides of the fireplace. Do not use drywall or other combustible in this area
(see illustration below).
The non-combustible facing must have an opening for the convection air outlet (see illustration
below).
The non-combustible facing may be attached to the front of the fireplace and non-combustible
framing with screws. Do not penetrate the fireplace more than 3/4”.
Facing over 1” thick (brick, thick marble) may be used around the perimeter of the faceplate.
NOTE:
leave a minimum of 1/8” between the top of the face and the surrounding facing material to
accommodate removal of the face.
Minimum 42"
Drywall
(or other combustible)
Framing Header
Non-Combustible Framing
(included with fireplace)
Non-Combustible Facing
(cement board, tile, marble, etc.)
Convection Air Outlet
(from upper manifold)
(use included trim if desired)
The facing will need to be
notched to go around the
bypass rod.