38 Installation
(for qualified installers only)
© Travis Industries
8/24/2017 - 1450
42 Apex CF
Electrical Line Hookup
Make sure the household breaker serving the fireplace is shut off prior to working on any electrical lines.
The electrical line leading to the junction box inside the fireplace must be installed by a qualified
installer and must meet all local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1.
The electrical line must supply 120 Volts, 60 Hz, and 10 amps (2A for blower, 8A for optional igniter).
Route the electrical supply line through the junction box cover plate and attach to the hookup wires
(see illustration below).
NOTE
: Details on the junction box are shown on the following page.
After all wiring is in place, replace the junction box cover and tighten the Romex clamps to secure the
wiring.
Wiring Diagram
Romex Clamps
Fireplace Junction Box
Black
White
Green
Black
White
Green
Blower Rheostat
Junction Box
Green
White
Black
Green
Black
White
POWER IN
Blower
Snap Disk
Combustor Temp Display
(& GreenStart) Power Lead
Inside of Junction Box