NSTALLATION
(C
ONT
.)
- For Qualified Installers Only!
P
AGE
7
Fireplace Placement Requirements
Minimum Framing Dimensions
¥
The 1/2" stand-offs on the back and sides and 6-1/4" stand-offs on the top of the fireplace are
designed to separate the fireplace from the framing members. These stand-offs may contact the
framing members but no material may be placed between the stand-offs.
AAAA
AAAA
AAAA
A
A
AAAA
AAAA
AAAA
AA
AA
AA
AA
AA
AA
AA
AA
AA
AA
AA
AA
A
AA
AA
A
Gas line (3/8" M.P.T. or 1/2"
F.P.T.) should be routed
6-5/8" behind the framing
opening and 1-7/8" above
the base of the fireplace (see
"Gas Line Connection" for
details).
43-1/4"
19-5/8"
46-1/2"
Route the electrical line to a
position at the right rear of
the fireplace.
If using a remote control or
thermostat, route the wire to
a location near the gas line
(include an extra 3' length for
hookup).
NOTE
: if venting directly to the rear,
make sure there is a min. 8-5/8" space
centered behind the fireplace for the
wall thimble. If a 90¡ elbow is used
directly off of the fireplace, the thimble
will be centered 51-1/4" above the
base of the fireplace.
¥
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
¥
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
¥
Due to the high temperature of the fireplace, it should be located out of traffic and away from
furniture and draperies.
Clearances
¥
When installed, walls in front of the fireplace must be a minimum 4-1/2" to the side of the faceplate.
¥
Fireplace must be placed so that no combustibles are within, or can swing within 36" of the front of
the fireplace (e.g. drapes, doors)
¥
Fireplace must be placed so the vents below and above the glass do not become blocked