12 Overview and repetition of paragraphs essential for safety
(2)
Read this first!
The whole section 2 is important to read!
(4)
Installation
(4.2.1)
For weight see Appendix 1, Data sheet. Suitable points to lift the unit are
shown in Appendix 2, Dimensional Drawing. The 3200 unit also has holes for
lifting eyes shown on the Dimensional Drawing. The unit should not be exposed
to strokes or knocks.
DO NOT LIFT THE UNIT USING THE PIPING
(4.6.10)
Make sure there is enough space around the unit to enable easy access
for service and maintenance, especially on the back gable side of the water
motor (opposite side of the concentrate pump).
(4.8.1)
Some units are equipped with an optional dosing return valve
, also DRV
in short. This valve is not to be used during regular operation and its
handle should remain positioned for dosing into the main water line only.
The valve should only be operated by qualified maintenance personnel for
maintenance/testing purposes.
(4.3.1)
FIREMIKS is designed to operate with clean water
. Water must be
free from sand, gravel and other debris that may wear out the volumetric water
motor quickly. In most cases the FIREMIKS can cope with occasional instances
of isolated foreign objects up to 2 mm size. If there is an acute risk of particles
entering the FIREMIKS or when polluted or contaminated water is used, the
piping system must be designed so that there is a suitable filter or strainer where
this pollution can be collected
fully
, placed
before
(upstream of) the FIREMIKS.
We refuse any responsibility for blockage or damage of the water motor by
any foreign objects in the water, whatever their size.
Please contact us if you
need further guidance in this subject.
(4.3.9)
Note! It is extremely important that a shut-off valve is installed
before the FIREMIKS unit.
This is to ensure a risk-free service/maintenance, i.e.
the risk for sudden rotation of the water motor due to unexpected water flow will
be eliminated by closing this valve. When working on the FIREMIKS, put a clear
sign on this valve stating:
“Do not open, maintenance work in progress”.
(4.3.11)
Note! As in all safety-related installations, there should always be a
back-up plan
. Never design the installation in such a way so that the water flow
through the FIREMIKS is the only source for fire-fighting water.
(4.10.1)
Note! Never let the FIREMIKS run dry without concentrate or
flushing water
. See 6.4.1 for more info.
(5)
Check before first start