4.6.1 The unit itself does not require any welding or painting for installation, suitable
pipe connections are to be bolted (cut groove) or threaded (BSP) and the unit
is held in place with screws, see 4.6.6. However, the supporting installation
can require welding and painting, in such case be careful not to contaminate
the in- and outlets of the FIREMIKS unit. It is not allowed to paint the
FIREMIKS unit.
4.6.2
The unit must be installed with the inlet and outlet of the water motor
and the pump shaft in horizontal positions (±5°).
Other configurations of
the FIREMIKS are possible but must be configured and approved by Firemiks
AB.
4.6.3 The unit should preferably be installed and used in a frost-free environment. If
this is not possible it is important to drain the unit completely before frost
season. It should not be exposed to higher temperature than 55 degrees
Celcius even when the unit is not in use. This is both valid for the ambient
temperature and for the water temperature.
Note! Be observant for direct solar radiation that can heat up the
unit above 55 degrees Celcius, in these cases use a sun roof.
Contact us if higher temperature tolerances, above 55 degrees
Celcius, are needed.
4.6.4 If the unit has been contaminated during storage, see also 4.1, make sure to
carefully clean the inside of the unit before installation. If contamination is
especially aggravated and/or temperature limits have been exceeded, please
contact your distributor or Firemiks AB on how to proceed.
4.6.5 The water flow must be in the direction shown by the arrow on the upper side
of the water motor (Note! The direction of rotation of the drive shaft is
reversed compared with the direction of the water flow arrow). The unit can
optionally be configured with the water flow in the opposite direction. See also
Appendix 2, Dimensional Drawing.
4.6.6 There are two methods of mounting the unit.
4.6.6.1 Using the Mounting feet on pump bracket (pump flange on the 450-3-F-FM)
With these feet, the unit can easily be mounted on a flat surface using bolts
to secure the unit. See Appendix 2, Dimensional Drawing for the key
dimensions of the mounting interface.
IMPORTANT: it is very important that the main water lines before and after
connected to the water motor are well fixated, or flexible couplings are used
to connect to the Firemiks. Be sure there is no movement that can forcefully
distort the pump bracket of the Firemiks which can lead to failure of the drive
gear alignment and ultimately the whole unit. Do not rely on the FIREMIKS
bracket as a support for the main water line. If unsure, the second below
method is more secure.
The 450-3-F-FM has mounting holes on the pump flange, however the unit
is cannot be mounted on a flat surface without suitable support brackets
which depending on the installation can be provided by Firemiks AB.