Integrated Fire Protection System
C
Trim Options
FM-076A-0-81C
Preaction trim options
1. Shut-off valve & sight glass
The shut-off valve & sight glass option is intended to be
used for applications where testing of the system operation
without filling the sprinkler piping network is desirable and
where it is critical that all functions of the preaction system
be tested under actual discharge conditions. Examples of
such applications are freezers, ovens, museums, data
processing and other hazards where the possibility of
water leaking from the piping system is to be avoided at all
costs.
Operation of the shut-off valve
Inspection of the system can be implemented without filling
the sprinkler piping network with water.
1.
CLOSE
the sprinkler piping network shut-off valve
(D4)
;
the valve is supervised on the same circuit as the main
water supply valve
(D1)
.
2.
OPEN
the main drain valve
(D3)
.
3. Simulate the operation of the system to open the deluge
valve
(A1)
;
see annual test under section
B
INSPECTION AND MAINTENANCE
. Using a flashlight in the
sight glasses, verify that water flows through the sight
glass assembly
(D5)
.
4. Once tests are completed, make sure the main drain
valve
(D3)
is completely
CLOSED
. Return the system in
service as per section
B
PLACING THE SYSTEM BACK IN
SERVICE
.
5. Fully
OPEN
the shut-off valve
(D4)
. Reset the release
control panel as per section
E
CONTROL BUTTONS
.
Warning :
Shut off valve
(D4)
is
not
available on 8"
(200 mm) system.
Figure 1 – Shut-off valve & sight glass
(figure is shown without cabinet for clarity)
FM-061H-0-75C
Sight glass
assembly (D5)
Point flash
light here
Main drain
valve (D3)
Supervised
shut-off valve (D4)
Supervised
main water
supply valve (D1)
2. Fire department connection
The fire department connection option consists of a
grooved tee fitting installed at the outlet of the deluge
valve
(A1)
. An access hole of the proper diameter is
factory pre-drilled on the right side of the
T
OTAL
P
AC
®
3
enclosure for connection going to the fire department
connection.
Note :
The fire department connection hardware itself
(drain, Siamese, etc.) is
not
provided with this option and
shall be provided by the installing contractor. Refer to
NFPA-13 Standards for additional information about the
equipment layout and installation.
Warning :
The fire department connection is
not
available
on 6" (150 mm) and 8" (200 mm) systems.
Figure 2 – Fire department connection
(figure is shown without cabinet for clarity)
Grooved tee fitting
with coupling & cap
Towards fire department
connection (hardware by
contractor)
FM-061H-0-76C