FireFlex TOTALPAC 3 Owner'S Operation & Maintenance Manual Download Page 12

Page 6 of 8

 

T

OTAL

P

AC

 

®

3

 

Integrated Fire Protection System

 

Mechanical Section - Non Interlock Preaction System - Pneumatic Release

 

 

FM-076A-0-41C 

1.8.3  Semi-annually 

  1.  Main water supply valve

 (D1)

  switch  shall be operated 

to verify the switch actuation upon movement of the 
hand wheel. 

  2.  Check alarm  pressure switch

 (C1)

  and optional water 

motor gong

 (C2)

 by opening the alarm test valve

 (B5)

.

 

  3.  Perform functional test of all components of the system. 

1.8.4  Annually 

  1.  Perform full flow  trip test  (see  paragraph 1.7.3  of the 

current section). 

  2.  Record indicating the date of the last trip, tripping time 

and name of the organization conducting the test shall 
be maintained at a location available for review by the 

AUTHORITY HAVING JURISDICTION

  3.  Perform  main  drain test  (see  paragraph 1.7.4  of the 

current section). 

1.8.5  Every 5 years 

  1.  Test on gauge (gauge precision required: less than 3% 

of the full scale). 

  2.  Perform test on control valve operation. 

  3.  Deluge  valve 

(A1)

  and their associated strainers, filters 

and restriction orifices shall be inspected internally. 

  4.  Perform main drain test  (see  paragraph 1.7.4  of the 

current section). 

2- Non interlock preaction system with 

pneumatic release 

Note:  

Numbers indicated between brackets refer to figure 1 

DETAILED SYSTEM TRIM SCHEMATICS

  from this section and 

section 

 D 

 

AIR SUPPLY

2.1 Normal condition 

  1.  Valves 

 

a)  Main water supply valve

 (D1)

 is 

OPEN

 

b)  All upstream water supply valves are 

OPEN

 

c)  Priming valve

 (B1)

 is 

OPEN

 

d)  Flow test valve

 (B6)

 is 

CLOSED

 

e)  Main drain valve

 (D3)

 is 

CLOSED

 

f)  Alarm test valve

 (B5)

 is 

CLOSED

 

g)  Manual emergency release valve

 (B10)

  is 

CLOSED

 

(handle in vertical position). 

 

h)  Air supply is 

OPEN

 (see section 

 D 

 AIR SUPPLY

). 

 

i)  All gauge valves are 

OPEN

 

j)  Shut-off valve

 (D4)

 is 

OPEN

 (if applicable). 

  3.  Gauges 

 

a)  Water supply  pressure 

(B12)

  shall not exceed 

175 PSI (1207 kPa) or 250 PSI (1724 kPa). 

 

b)  Priming chamber  pressure 

(B11)

  should be equal to, 

or higher than, water supply pressure 

(B12)

 

c)  System piping network 

(E3 

and

 F4)

 shall be at 35 PSI 

(242 kPa) or 55 PSI  (380 kPa)  (see  section 

 D 

  AIR 

SUPPLY

). 

 

d)  Pneumatic release piping network (pilot line) 

(E13)

 

shall be 35 PSI  (242 kPa) or 55 PSI  (380 kPa) (see 
section 

 D 

 AIR SUPPLY

). 

  4.  Pressure switches & settings (factory set) 

 

a)  Alarm  pressure  switch 

(C1)

  should activate when 

pressurized higher than 5 PSI (34 kPa). 

 

b)  Low air pressure  switch 

(E4)

  should activate when 

pressurized lower than 25 PSI  (173 kPa) or 45 PSI 
(311 kPa) (see section 

 D 

 AIR SUPPLY

). 

 

c)  Pilot line low air pressure switch 

(E14)

 should activate 

when pressurized lower than 25 PSI  (173 kPa) or 
45 PSI (311 kPa) (see section 

 D 

 AIR SUPPLY

). 

 

Summary of Contents for TOTALPAC 3

Page 1: ...FM 076A 0 1C Advanced Integrated Fire Protection System TOTALPAC 3 Owner s Operation and Maintenance Manual NON INTERLOCK PREACTION SYSTEM PNEUMATIC RELEASE...

Page 2: ...ual is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Page 3: ...4 System operation 1 5 Emergency instructions 1 6 Placing the system back in service after operation 1 7 Inspections tests 1 8 Maintenance 2 System trim 2 1 Normal condition Trim Options Section C 1...

Page 4: ...Page iv TOTALPAC 3 Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL FM 076A 0 1C This page is left intentionally blank...

Page 5: ...unit is identified with its unique serial number This number is located on an adhesive label inside the main door panel and is used to maintain a record in our computerized data base Have this serial...

Page 6: ...he following diameters 1 40 mm 3 80 mm 6 150 mm 2 50 mm 4 100 mm 8 200 mm TOTALPAC 3 preaction system is supplied with groove groove deluge valve Unit with flange flange deluge valve is also available...

Page 7: ...l inspection sequence see paragraph 1 8 of the current section 9 If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or F...

Page 8: ...e priming chamber of the deluge valve A1 through the priming line which includes a normally open priming valve B1 strainer B2 restricted orifice B3 and spring loaded check valve B4 Water supply pressu...

Page 9: ...ce for an extended period of time all water must be removed from the priming chamber trim piping water supply piping and any other trapped areas 1 6 Placing the system back in service after operation...

Page 10: ...supply valve D1 10 When full flow develops from the flow test valve B6 CLOSE the flow test valve Verify there is no flow from drip check valve B7 when the plunger is pushed 11 FULLY OPEN the main wate...

Page 11: ...wner is responsible for maintaining the fire protection system and devices in proper operating condition The system shall be maintained in full operation condition at all times All troubles or impairm...

Page 12: ...se Note Numbers indicated between brackets refer to figure 1 DETAILED SYSTEM TRIM SCHEMATICS from this section and section D AIR SUPPLY 2 1 Normal condition 1 Valves a Main water supply valve D1 is OP...

Page 13: ...7 2 B9 B2 TOTALPAC 3 Base shown without enclosure FM 061H 0 102C Trim components A1 Deluge valve B1 Priming valve N O B2 Strainer B3 1 16 1 6 mm Restricted orifice B4 Spring loaded check valve B5 Alar...

Page 14: ...Page 8 of 8 TOTALPAC 3 B Integrated Fire Protection System Mechanical Section Non Interlock Preaction System Pneumatic Release FM 076A 0 41C This page is left intentionally blank...

Page 15: ...sure the main drain valve D3 is completely CLOSED Return the system in service as per section B PLACING THE SYSTEM BACK IN SERVICE 5 Fully OPEN the shut off valve D4 Reset the release control panel as...

Page 16: ...utside face of the mounting base or cabinet surface On skid unit the surface of the flange on the outlet riser will always be 6 inches above the dimension shown on the dimensional data of the system o...

Page 17: ...dry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an APMD air pressure maintenance device trim factory mounted in the TOTALPAC 3 cabinet The APMD regulate...

Page 18: ...one shot Proceed by steps 3 OPEN the main drain valve D3 and let the pressure drop until the air compressor restarts Check pressure reading on the system pressure gauge when the air compressor stops a...

Page 19: ...valve head entirely off while the compressor is operating Ejection of valve parts could cause severe injury 3 2 Air supply Style B or C refer to figure 3 or 4 The Viking Model D 2 APMD air pressure ma...

Page 20: ...7 kPa 35 PSI 241 kPa 25 PSI 172 kPa B or D 35 PSI 241 kPa n a n a 25 PSI 172 kPa Release pilot line C 35 PSI 241 kPa n a n a 25 PSI 172 kPa Table 3 Water pressure from 175 PSI to 250 PSI 1207 kPa to 1...

Page 21: ...plugged with SureFire or non interlock preaction trim Pressure relief valve FM 061H 0 118C 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR TO SPRINKLER RISER E9 Air style...

Page 22: ...im This section replaced by Dehydrator option when used Contractor external Air or Nitrogen connection E7 E6 3 TO PNEUMATIC ACTUATOR plugged when not used FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TES...

Page 23: ...c actuator E14 E6 FM 061H 0 120B E5 To pneumatic release piping network E13 To optional accelerator plugged when not used Contractor external air or Nitrogen connection Air style components E5 APMD ai...

Page 24: ...E16 E3 TO OPTIONAL ACCELERATOR plugged when not used Contractor external air or Nitrogen connection E6 3 TO PNEUMATIC ACTUATOR plugged when not used Warning The external air supply must be restricted...

Page 25: ...t Viking P N 16854 which includes the dehydrator desiccant and mounting brackets 9 The unit is to be used on compressed air service only Operation of dehydrator The dehydrator directs the incoming air...

Page 26: ...H 0 124B 1 From air supply Desiccant sight glass To sprinkler riser Dehydrator bowl Figure 7 Dehydrator option for air supply Style B To air Style B trim E12 Desiccant sight glass B13 E14 To drain col...

Page 27: ...itches adjustments 1 CLOSE the isolation valve of the accelerator Refer to instructions described on Viking datasheet 122 form No 071692 To reset the accelerator device Make sure the system is properl...

Page 28: ...ed Fire Protection System Air Supply Preaction System FM 076A 0 86C Figure 8 Accelerator Option For preaction system and pilot line release Upper chamber pressure gauge Drain plug To air line Accelera...

Page 29: ...red to a terminal strip TBA TBC for contractor s field wiring see figure 2 and the section F ELECTRICAL SECTION 1 2 Technical data Steel enclosure Refer to section G CABINET SECTION for further detail...

Page 30: ...l SYSTEM DEVICES OPT FM 061H 0 151A Factory Wired Air Compressor or Excess Pressure Pump Isolating Switch E15 AC POWER 120VAC 50 60Hz or 220 240VAC 50 60Hz All conduits are installed by the Contractor...

Page 31: ...building s Central Fire Alarm Panel OPTIONAL LOS ANGELES OPTION CHICAGO OPTION NOTE All devices are shown in their normal supervisory state NOTES Use dry contacts with power limited circuits only Cont...

Page 32: ...Page 2 of 2 TOTALPAC 3 F Integrated Fire Protection System Electrical Section Non Interlocked Preaction System Pneumatic Release FM 076A 0 61C This page is left intentionally blank...

Page 33: ...ressure system air pressure and priming water pressure are all visible through clear Lexan windows Multiple units installation is easily achieved by jointing manifold sections together at their water...

Page 34: ...3 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 77 1956 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 38 965 42 1067 34 883 44 1130 48 1232 3 80 4 102 3 76 2 51 35 90...

Page 35: ...m 21 530mm Figure 3 Cabinet doors clearance detail TOTALPAC 3 UNIT FM 061H 0 275A 1 B min C min A min B min TYPICAL MECHANICAL ROOM Figure 4 Knockouts details 2 Typ 65mm 9 230mm High voltage Low volta...

Page 36: ...50mm 2 50mm 8 200mm 12 305mm 17 445mm 2 50mm Figure 6 Open drain details for multiple units refer to dimensions in table 5 TOTALPAC 3 Unit Shown Without Front Doors Drain Collector running between wal...

Page 37: ...phosphate base Multiple units installation is easily achieved by jointing manifold sections together at their water inlets Drains outlet shall remain separate and open for each unit Refer to figure 1...

Page 38: ...292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 37 953 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 659 38 965 42 1067 34 88...

Page 39: ...40mm 25 635mm 15 380mm 2 50mm 25 635mm 15 380mm 3 80mm 37 959mm 15 380mm 4 100mm 37 959mm 15 380mm 6 150mm 48 1220mm 15 380mm Figure 9 Skid clearance detail B min A min TYPICAL MECHANICAL ROOM TOTALP...

Page 40: ...55mm 13 350mm 2 50mm 6 150mm 11 280mm 13 350mm 2 50mm Figure 11 Open drain details for multiple units refer to dimensions in table 10 B Typical Air Gap A Water Supply Pipe Can Be Manifolded Drain Coll...

Page 41: ...its inconveniences transportation charges or other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some juri...

Page 42: ...Page 2 of 2 TOTALPAC 3 H Integrated Fire Protection System Limited Warranty FM 076A 0 96C User Notes...

Reviews: