Page 6 of 8
T
OTAL
P
AC
®
3
B
Integrated Fire Protection System
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1.8.3 Semi-annually
1. Main water supply valve
(D1)
switch shall be operated
to verify the switch actuation upon movement of the
hand wheel.
2. Check alarm pressure switch
(C1)
and optional water
motor gong
(C2)
by opening the alarm test valve
(B5)
.
3. Perform functional test of all components of the system.
1.8.4 Annually
1. Perform full flow trip test (see paragraph 1.7.3 of the
current section).
2. Record indicating the date of the last trip, tripping time
and name of the organization conducting the test shall
be maintained at a location available for review by the
AUTHORITY HAVING JURISDICTION
.
3. Perform main drain test (see paragraph 1.7.4 of the
current section).
1.8.5 Every 5 years
1. Test on gauge (gauge precision required: less than 3%
of the full scale).
2. Perform test on control valve operation.
3. Deluge valve
(A1)
and their associated strainers, filters
and restriction orifices shall be inspected internally.
4. Perform main drain test (see paragraph 1.7.4 of the
current section).
2- Non interlock preaction system with
pneumatic release
Note:
Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS
from this section and
section
D
AIR SUPPLY
.
2.1 Normal condition
1. Valves
a) Main water supply valve
(D1)
is
OPEN
.
b) All upstream water supply valves are
OPEN
.
c) Priming valve
(B1)
is
OPEN
.
d) Flow test valve
(B6)
is
CLOSED
.
e) Main drain valve
(D3)
is
CLOSED
.
f) Alarm test valve
(B5)
is
CLOSED
.
g) Manual emergency release valve
(B10)
is
CLOSED
(handle in vertical position).
h) Air supply is
OPEN
(see section
D
AIR SUPPLY
).
i) All gauge valves are
OPEN
.
j) Shut-off valve
(D4)
is
OPEN
(if applicable).
3. Gauges
a) Water supply pressure
(B12)
shall not exceed
175 PSI (1207 kPa) or 250 PSI (1724 kPa).
b) Priming chamber pressure
(B11)
should be equal to,
or higher than, water supply pressure
(B12)
.
c) System piping network
(E3
and
F4)
shall be at 35 PSI
(242 kPa) or 55 PSI (380 kPa) (see section
D
AIR
SUPPLY
).
d) Pneumatic release piping network (pilot line)
(E13)
shall be 35 PSI (242 kPa) or 55 PSI (380 kPa) (see
section
D
AIR SUPPLY
).
4. Pressure switches & settings (factory set)
a) Alarm pressure switch
(C1)
should activate when
pressurized higher than 5 PSI (34 kPa).
b) Low air pressure switch
(E4)
should activate when
pressurized lower than 25 PSI (173 kPa) or 45 PSI
(311 kPa) (see section
D
AIR SUPPLY
).
c) Pilot line low air pressure switch
(E14)
should activate
when pressurized lower than 25 PSI (173 kPa) or
45 PSI (311 kPa) (see section
D
AIR SUPPLY
).