2 Integrated Fire Protection System 

PAR-3 Control Panel 

 

 

FM-072G-0-05 C

 

TROUBLE SHOOTING: 

SYMPTOMS PROBLEM 

SOLUTION 

Circuit trouble LED 
ON 

Notification appliance circuit trouble 

1.

  Check TBA for proper connections. 

2.

  Remove all field wiring and install dummy 

ELR at ourput circuit.  Check for supervisory 
voltage across it (normal –2,3V), if problem 
persists, replace circuit board. 

3.

  Remove dummy ELR, reconnect field wiring 

and measure voltage across output; (tourble – 
5V, short 0V). 

4.

  Check for ELR at last device. 

5.

  Check field wiring. 

Any of the right 
column yellow LEDs 
flashing 

Initiating zone open circuit trouble 

1.

  Check TBA for proper connections. 

2.

  Remove field wiring for zone in trouble and 

install dummy ELR (4,7K for 24V; 2,2K for 
12V).  If problem persists, replace circuit 
board. 

Any of the right 
column yellow LED 
steady ON 

Zone disable 

Check ZONE DISABLE section 

Missing or 
Disconnected 

Check battery connections 

Battery trouble Batt 
yellow LED ON 

Low or damaged 
battery 

1.

  Remove batteries, check voltage across 

charger output (17 to 19V for 24V; 8-10V for 
12V), otherwise, replace circuit board. 

2. 

 Reconnect batteries, measure battery 

voltage at battery terminals.  If voltage is less 
than 85% of rated voltage, allow them to 
charge for 48 hours. 

3.

  If problem persists, replace batteries. 

Ground fault trouble Earth yellow LED 
ON 

1.

  Remove field wiring from TBA.  Install 

dummy ELR (4,7K for 24V, 2,2K for 12V). 

2.

  Remove both battery leads. 

3.

  If trouble clears, connect one circuit at the 

time to pinpoint the problem. 

4.

  If trouble does not clear, replace circuit 

board. 

System Trouble LED 
ON 

Power trouble LED 
ON 

OPT1, OPT2 jumper cutted 

Install optional module or replace jumper if 
module is not used. 

Any of the right column red LEDs ON 

Short on initiating circuit wiring 

Remove field wiring and install ELR.  If trouble 
clears, look for faulty or incorrectly wired 
devices. 

4XZM:  Associated LED doesn't activate for 
alarm, trouble or supervisory conditions. 

Optional module trouble 

1.

  Make sure module is properly installed. 

2.

  Move disable switch SW1 on 4XZM to the 

left. 

RZA-4X buzzer doesn't sound for alarm, 
trouble or supervisory conditions. 

4XLM 

1.

  Make sure that the 4XLM module is 

installed on J7 and J8. 

2.

  Check field wiring. 

All RZA-4X LEDs stay ON 

Power wasn't removed prior to 
installation 

Press system reset. 

AC Power LED ON 

Micro Fail yellow LED ON 

Microprocessor damaged. 

Replace circuit board. 

Loss of main power 

Check incoming power (TBB). 

System trouble LED ON 

Damaged circuit breaker 

Replace circuit board. 

AC power LED OFF 

Micro Fail yellow LED ON 

Microprocessor damaged. 

Replace circuit board. 

 

 

Summary of Contents for TOTALPAC 2 PAR-3

Page 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...

Page 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...

Page 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...

Page 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...

Page 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...

Page 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...

Page 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...

Page 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...

Page 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...