AC

2 Integrated Fire Protection System 

PAR-3 Control Panel 

 

 

FM-072G-0-05 C 

 

 

6. System Status LEDs:

   

Alarm, Trouble and Supervisory LEDs will flash on and off 
until the event(s) has been acknowledged (TONE or 
ALARM SILENCE), at which point the LED will illuminate 
steadily. 

AC POWER:  

Green LED that illuminates steadily to 

indicate presence of AC power. 

SYSTEM ALARM:  

Red LED that flashes when an alarm 

occurs. 

SOLENOID OPERATED:

  Red LED that illuminates 

steadily when the solenoid valve is activated. 

SUPERVISORY:

  Yellow LED that flashes upon activation 

of a supervisory device (main valve or Low air pressure). 

SYSTEM TROUBLE:  

Yellow LED that flashes for any 

trouble condition, including those associated with option 
boards. 

CIRCUIT TROUBLE:  

Yellow LED that flashes for trouble 

conditions on output circuits. 

ALARM SILENCED:  

Yellow LED that illuminates steadily 

when the ALARM SILENCE switch has been pushed after 
an alarm. 

POWER TROUBLE:  

Yellow LED that flashes for low or 

disconnected batteries and earth fault conditions. 

BATT:

  Yellow LED that illuminates steadily on 

motherboard when battery is low or not detected. 

EARTH:

  Yellow LED that illuminates steadily on 

motherboard during a ground fault condition. 

MICRO FAIL: 

Yellow LED that illuminates on motherboard 

when watchdog timer detects microprocessor failure. 

Control Switches:

 

TONE SILENCE:  

Acknowledge alarms, troubles and 

supervisory.  The panel has alarm and trouble resound 
with LED flash of new conditions.   

The flashing trouble LED(s) illuminate steadily on TONE 
SILENCE and the buzzer silences.   
A Second trouble will resound the piezo. The piezo has 
three sounds for alarm, trouble, and supervisory.  Trouble 
conditions are self restoring.  Alarms and supervisories 
latch and require RESET to clear. 

ALARM SILENCE:  

Acknowledge for alarms and 

supervisories.  The ALARM SILENCE switch will silence 
the local piezo, change any flashing alarm LEDs to steady, 
and turn off the notification appliance circuits (

not the 

Releasing Circuits

).  The "ALARM SILENCED" LED will 

illuminate.  Alarm silence is a latching function and 
requires a RESET to clear. 

ALARM ACTIVATE:  

The ALARM ACTIVATE switch may 

be used to activate Notification Appliance Circuits. 

 

ALARM ACTIVATE also activates the System Alarm relay.  
ALARM ACTIVATE is a latching function.  Pressing 
ALARM SILENCE silences the notification appliance 
circuits and System Alarm Relay and lights the Alarm 
Silenced LED.  Pressing RESET returns the system to 
normal. 

SYSTEM RESET:  

The RESET switch breaks power to all 

initiating circuits, 4-wire smoke power and option boards 
and will clear any activated output circuits.  If any alarm or 
trouble still exists after reset, they will reactivate the panel.  
Holding RESET down will perform a LAMP TEST function 
and will activate the buzzer. 

Zone Status LED(s): 

The alarm and/or trouble LED(s) will flash until the 
event(s) has been acknowledged (TONE or ALARM 
SILENCE), at which point the LED(s) will illuminate 
steadily.  See detail below for the various configurations: 

 

Double Interlocked 

Preaction 

Electric / Pneu

Lectric

 

Deluge 

ALARM LED

TROUBLE LED

ALARM LED

TROUBLE LED

ALARM LED

TROUBLE LED

(NOT USED)

TROUBLE LED

Double Interlocked 

Preaction 

Electric / Pneumatic

 

Double Interlocked 

Preaction 

Elevator Configuration

 

Single Interlocked 

Preaction 

DETECTION

ZONE 1

WATER FLOW

LOW  AIR PRESS.

OR MAIN VALVE

WATER FLOW

LOW  AIR PRESS.

OR MAIN VALVE

DETECTION

ALARM LOW AIR

PRESSURE

SYSTEM

PRESSURIZED

LOW  AIR PRESS.

OR MAIN VALVE

DETECTION

ZONE 2

DETECTION

ZONE 1

DETECTION

ZONE 2

WATER FLOW

LOW  AIR PRESS.

OR MAIN VALVE

DETECTION

ZONE 1

ELEVATOR AT

DESIGNATED

LOBBY

FAIL SAFE TIMER

DETECTION

ZONE 1

DETECTION

ZONE 2

WATER FLOW

MAIN VALVE

CONFIGURATION: 

Summary of Contents for TOTALPAC 2 PAR-3

Page 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...

Page 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...

Page 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...

Page 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...

Page 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...

Page 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...

Page 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...

Page 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...

Page 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...

Page 10: ...Page 10 of 10 TOTALPAC2 Integrated Fire Protection System PAR 3 Control Panel FM 072G 0 05 C ...

Reviews: