Page 6 of 10
T
OTAL
P
AC
2 Integrated Fire Protection System
PAR-3 Control Panel
FM-072G-0-05 C
6. System Status LEDs:
Alarm, Trouble and Supervisory LEDs will flash on and off
until the event(s) has been acknowledged (TONE or
ALARM SILENCE), at which point the LED will illuminate
steadily.
AC POWER:
Green LED that illuminates steadily to
indicate presence of AC power.
SYSTEM ALARM:
Red LED that flashes when an alarm
occurs.
SOLENOID OPERATED:
Red LED that illuminates
steadily when the solenoid valve is activated.
SUPERVISORY:
Yellow LED that flashes upon activation
of a supervisory device (main valve or Low air pressure).
SYSTEM TROUBLE:
Yellow LED that flashes for any
trouble condition, including those associated with option
boards.
CIRCUIT TROUBLE:
Yellow LED that flashes for trouble
conditions on output circuits.
ALARM SILENCED:
Yellow LED that illuminates steadily
when the ALARM SILENCE switch has been pushed after
an alarm.
POWER TROUBLE:
Yellow LED that flashes for low or
disconnected batteries and earth fault conditions.
BATT:
Yellow LED that illuminates steadily on
motherboard when battery is low or not detected.
EARTH:
Yellow LED that illuminates steadily on
motherboard during a ground fault condition.
MICRO FAIL:
Yellow LED that illuminates on motherboard
when watchdog timer detects microprocessor failure.
Control Switches:
TONE SILENCE:
Acknowledge alarms, troubles and
supervisory. The panel has alarm and trouble resound
with LED flash of new conditions.
The flashing trouble LED(s) illuminate steadily on TONE
SILENCE and the buzzer silences.
A Second trouble will resound the piezo. The piezo has
three sounds for alarm, trouble, and supervisory. Trouble
conditions are self restoring. Alarms and supervisories
latch and require RESET to clear.
ALARM SILENCE:
Acknowledge for alarms and
supervisories. The ALARM SILENCE switch will silence
the local piezo, change any flashing alarm LEDs to steady,
and turn off the notification appliance circuits (
not the
Releasing Circuits
). The "ALARM SILENCED" LED will
illuminate. Alarm silence is a latching function and
requires a RESET to clear.
ALARM ACTIVATE:
The ALARM ACTIVATE switch may
be used to activate Notification Appliance Circuits.
ALARM ACTIVATE also activates the System Alarm relay.
ALARM ACTIVATE is a latching function. Pressing
ALARM SILENCE silences the notification appliance
circuits and System Alarm Relay and lights the Alarm
Silenced LED. Pressing RESET returns the system to
normal.
SYSTEM RESET:
The RESET switch breaks power to all
initiating circuits, 4-wire smoke power and option boards
and will clear any activated output circuits. If any alarm or
trouble still exists after reset, they will reactivate the panel.
Holding RESET down will perform a LAMP TEST function
and will activate the buzzer.
Zone Status LED(s):
The alarm and/or trouble LED(s) will flash until the
event(s) has been acknowledged (TONE or ALARM
SILENCE), at which point the LED(s) will illuminate
steadily. See detail below for the various configurations:
Double Interlocked
Preaction
Electric / Pneu
Lectric
Deluge
ALARM LED
TROUBLE LED
ALARM LED
TROUBLE LED
ALARM LED
TROUBLE LED
(NOT USED)
TROUBLE LED
Double Interlocked
Preaction
Electric / Pneumatic
Double Interlocked
Preaction
Elevator Configuration
Single Interlocked
Preaction
DETECTION
ZONE 1
WATER FLOW
LOW AIR PRESS.
OR MAIN VALVE
WATER FLOW
LOW AIR PRESS.
OR MAIN VALVE
DETECTION
ALARM LOW AIR
PRESSURE
SYSTEM
PRESSURIZED
LOW AIR PRESS.
OR MAIN VALVE
DETECTION
ZONE 2
DETECTION
ZONE 1
DETECTION
ZONE 2
WATER FLOW
LOW AIR PRESS.
OR MAIN VALVE
DETECTION
ZONE 1
ELEVATOR AT
DESIGNATED
LOBBY
FAIL SAFE TIMER
DETECTION
ZONE 1
DETECTION
ZONE 2
WATER FLOW
MAIN VALVE
CONFIGURATION: