AC
2 Integrated Fire Protection System
PAR-3 Control Panel
FM-072G-0-05 C
Page 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...
Page 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...
Page 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...
Page 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...
Page 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...
Page 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...
Page 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...
Page 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...
Page 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...
Page 10: ...Page 10 of 10 TOTALPAC2 Integrated Fire Protection System PAR 3 Control Panel FM 072G 0 05 C ...