FireFlex TOTALPAC 2 PAR-3 Manual Download Page 7

 

 

Page 7 of 10

 

T

OTAL

P

AC

2 Integrated Fire Protection System 

PAR-3 Control Panel 

 

 

FM-072G-0-05 C

 

7.  Zone Disable: 

Disabling a detection or a supervisory zone will prevent 
the internal audible signal in the control panel or any 
output circuit from activating upon activation of a 
detection device in this zone.  All four entry zones can be 
disabled. 

Note:

 

 

The system could become non-operational 

depending on the zones being disabled.  Furthermore, 
the control panel must not be in alarm condition to effect 
this function.

 

.1  To disable a zone, the following routine must be 

followed: 

.a  Press the button identified 

TONE SILENCE

 and hold 

it until all lamps go out. 

.b  While holding the button identified 

TONE SILENCE

press the following buttons in this order:  

ALARM 

SILENCE

ALARM ACTIVATE

 and then 

SYSTEM 

RESET

Note:

 

 

Do not release the button identified 

TONE 

SILENCE

 until the routine is completed. 

.c  The red lamp identified 

DETECTION

 or 

DETECTION 

ZONE X

  will now begin to flash. 

.d  To disable that zone, press the button identified 

SYSTEM RESET

.  A disabled zone is identified by 

an illuminated yellow lamp on the zone. 

Note:

  The button identified

 SYSTEM RESET

 operates 

alternately; therefore press this button again to 
reactivate the zone. 

.2  To select the next zone, simply press the button 

identified 

ALARM SILENCE

.  To select the previous 

zone, press the button identified 

ALARM ACTIVATE

.a  When selection of the disabled zones is completed, 

release the button identified 

TONE SILENCE

.b  The yellow lamp identified 

SYSTEM TROUBLE

 will 

flash.  Silence the audible signal by pressing the 
button identified 

TONE SILENCE

.3  To reactivate the zones previously disabled, repeat the 

procedure to disable the zones.  Pressing the button 
identified

 SYSTEM RESET

 will deactivate the yellow 

lamp of the selected zone, and thus reactivate the zones 
that were disabled. 

Note:  

Resetting the control panel will not reactivate the 

disabled zones.  However if the control panel is in alarm 
condition and you wish to reactivate zones that were 
previously disabled, then the control panel must be 
reset. 

8.  Last Event recall: 

This function allows the user to review the previous 
condition of the control panel. 

Note:

 

 

The control panel must not be in alarm condition 

when performing this function.

 

To recall the last event, the following routine must be 
followed: 

.1  Press the button identified 

TONE SILENCE

 and hold it 

until all lamps go out. 

.2 

While holding the button identified 

TONE SILENCE

press the following buttons in this order: 

SYSTEM 

RESET, ALARM ACTIVATE

 and then 

ALARM 

SILENCE. 

.3  The lamps in the control panel will indicate the previous 

condition since the last control panel reset. 

.4  Release the button identified 

TONE SILENCE

 to return 

to the normal operation mode. 

 

 

 

Summary of Contents for TOTALPAC 2 PAR-3

Page 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...

Page 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...

Page 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...

Page 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...

Page 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...

Page 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...

Page 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...

Page 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...

Page 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...

Page 10: ...Page 10 of 10 TOTALPAC2 Integrated Fire Protection System PAR 3 Control Panel FM 072G 0 05 C ...

Reviews: