2 Integrated Fire Protection System
PAR-3 Control Panel
FM-072G-0-05 C
7. Zone Disable:
Disabling a detection or a supervisory zone will prevent
the internal audible signal in the control panel or any
output circuit from activating upon activation of a
detection device in this zone. All four entry zones can be
disabled.
Note:
The system could become non-operational
depending on the zones being disabled. Furthermore,
the control panel must not be in alarm condition to effect
this function.
.1 To disable a zone, the following routine must be
followed:
.a Press the button identified
TONE SILENCE
and hold
it until all lamps go out.
.b While holding the button identified
TONE SILENCE
,
press the following buttons in this order:
ALARM
SILENCE
,
ALARM ACTIVATE
and then
SYSTEM
RESET
.
Note:
Do not release the button identified
TONE
SILENCE
until the routine is completed.
.c The red lamp identified
DETECTION
or
DETECTION
ZONE X
will now begin to flash.
.d To disable that zone, press the button identified
SYSTEM RESET
. A disabled zone is identified by
an illuminated yellow lamp on the zone.
Note:
The button identified
SYSTEM RESET
operates
alternately; therefore press this button again to
reactivate the zone.
.2 To select the next zone, simply press the button
identified
ALARM SILENCE
. To select the previous
zone, press the button identified
ALARM ACTIVATE
.
.a When selection of the disabled zones is completed,
release the button identified
TONE SILENCE
.
.b The yellow lamp identified
SYSTEM TROUBLE
will
flash. Silence the audible signal by pressing the
button identified
TONE SILENCE
.
.3 To reactivate the zones previously disabled, repeat the
procedure to disable the zones. Pressing the button
identified
SYSTEM RESET
will deactivate the yellow
lamp of the selected zone, and thus reactivate the zones
that were disabled.
Note:
Resetting the control panel will not reactivate the
disabled zones. However if the control panel is in alarm
condition and you wish to reactivate zones that were
previously disabled, then the control panel must be
reset.
8. Last Event recall:
This function allows the user to review the previous
condition of the control panel.
Note:
The control panel must not be in alarm condition
when performing this function.
To recall the last event, the following routine must be
followed:
.1 Press the button identified
TONE SILENCE
and hold it
until all lamps go out.
.2
While holding the button identified
TONE SILENCE
,
press the following buttons in this order:
SYSTEM
RESET, ALARM ACTIVATE
and then
ALARM
SILENCE.
.3 The lamps in the control panel will indicate the previous
condition since the last control panel reset.
.4 Release the button identified
TONE SILENCE
to return
to the normal operation mode.