background image

                  411UD     Document #50759   Rev. E   12/09/2008   P/N 50759:E

61

Ademco Contact ID Format Event Code Description

EVENT

MESSAGE

Sounder/Relay Disables - 520
520 Sounder/Relay disable 

DISABLE - Sounder/Relay - #

521 Bell 1 disable

DISABLE - Bell/Siren - #1

522 Bell 2 disable

DISABLE - Bell/Siren - #2

523 Alarm relay disable

DISABLE - Alarm Relay

524 Trouble relay disable

DISABLE - Trouble Relay

525 Reversing relay disable

DISABLE - Reversing Relay

526 Bell 3 disable

DISABLE - Bell/Siren - #3

527 Bell 4 disable

DISABLE - Bell/Siren - #4

System Peripheral Disables - 530 and 540

Communication Disables - 550 and 560
551 Dialer disabled

DISABLE - Dialer Disable

552 Radio transmitter disabled

DISABLE - Radio Disable

Bypasses - 570
570 Zone bypass

BYPASS - Zone Bypass - #

571 Fire bypass

BYPASS - Fire Bypass - #

572 24-Hour zone bypass

BYPASS - 24-Hour Bypass - #

573 Burglar bypass

BYPASS - Burg. Bypass - #

574 Group bypass

BYPASS - Group Bypass - #

Test Misc. - 600
601 Manual trigger test

TEST - Manually TriggeredRestore not applicable

602 Periodic test report

TEST - Periodic

Restore not applicable

603 Periodic RF transmission

TEST - Periodic Radio

Restore not applicable

604 Fire test

TEST - Fire Test

Restore not used

605 Status report to follow

STATUS - Status Follows Restore not applicable

606 Listen-in to follow

LISTEN - Listen-in ActiveRestore not applicable

607 Walk test mode

TEST - Walk Test Mode

608 System abnormal test

TEST - System Abnormal Test

Summary of Contents for FireWatch 411UD

Page 1: ...Digital Alarm Communicator Transmitter 411UD P N 50759 E ECN 08 879 E Document 50759 12 09 2008 Rev 2009 ...

Page 2: ...s especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper stor age of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise...

Page 3: ...d Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board locatio...

Page 4: ...4 411UD Document 50759 Rev E 12 09 2008 P N 50759 E Notes ...

Page 5: ...4 CHAPTER 2 Installation 15 Mounting Options 15 411UD Enclosure 15 Operating Power 15 Input Channels 15 Typical FACP Connection to 411UD 16 Style B Channel Connections 17 Output Circuits 17 Programmable Relay 17 Telephone Circuits 18 Wiring Phone Jacks 18 Optional Programmer 19 Programmer Connection to 411UD 19 UL Power limited Wiring Requirements 20 CHAPTER 3 Modes of Operation 21 Normal Mode 21 ...

Page 6: ...ry Central Station 54 4 2 Standard 4 2 Express Formats Secondary Central Station 54 4 2 Standard 4 2 Express Formats Primary Central Station 55 4 2 Standard 4 2 Express Formats Secondary Central Station 55 All 3 1 All 4 1 and 4 2 Expanded Formats for Primary Central Station 56 All 3 1 All 4 1 and 4 2 Expanded Formats for Secondary Central Station 56 All 3 1 All 4 1 and 4 2 Expanded Formats for Pri...

Page 7: ...s for Fire Protective Signaling Systems UL 1076 Proprietary Burglar Alarm Units and Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1635 Digital Alarm Communicator System Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN ULC S524 01 Standard for Installation of Fire Alarm Systems CAN ULC S527 99 Standard for Control Units for Fire ...

Page 8: ...1 671 cm X 1 00 2 54 cm metal enclosure providing a variety of mounting options 1 1 Product Features Four input channels Dual telephone lines Dual telephone line voltage detect Alternating phone lines for 24 hour test messages Program locations for entering up to 20 digit central station and service terminal telephone numbers Surface mount technology Compact in size Separate external keypad and di...

Page 9: ...ecifications Operating Power The 411UD may be powered from UL listed control panels that output nonresettable and power limited 12 or 24 VDC power The configuration of Jumper J4 determines whether 12 VDC power is to be supplied directly to the 411UD circuit board or 24 VDC power is to be supplied and then internally regulated down internally to 12 VDC DC Power TB1 Terminals 4 and 5 Terminal 6 is E...

Page 10: ...mmunicator may be a power limited filtered nonresettable nominal 12 VDC 11 2 to 12 4 VDC UL tested range 15 10 or nominal 24 VDC 21 3 to 24 0 VDC UL tested range 15 10 Jumper J4 is used to select the power source 1 3 2 Channels Inputs Four input channels are provided on the 411UD digital communicator which are used for connection to the control panel being monitored Each input can be programmed to...

Page 11: ...1 or 2 communication fault total communica tion failure and communications disabled Front Panel Indicators Communication Fail yellow LED DACT Trouble yellow LED Channel Active red LED Circuit Board Indicators Primary Phone Line 1 PH1 Active red LED Secondary Phone Line 2 PH2 Active red LED Modem Active green LED TB2 TB1 R41 U8 U10 U11 J2 PH1 PH2 J1 J4 FIGURE 1 2 411UD Controls and Indicators Chann...

Page 12: ... on page 41 1 6 Telephone Requirements and Warnings 1 6 1 Telephone Circuitry PH1 PH2 AC Ringer Equivalence Number REN 0 5B DC Ringer Equivalence Number REN 1 3 Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold less than 4 0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telep...

Page 13: ...eans that the equip ment meets certain telecommunications network protective operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document s The Department does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of ...

Page 14: ...er to change the digital communicator s internal 24 hour clock Connecting an external Programmer allows access to the various Modes of operation While the communicator is in Real Time Clock Mode it does not monitor channel inputs 1 7 3 Program Mode Program Mode is used to change the programmed functions of the 411UD digital communicator While the commu nicator is in Program Mode it does not monito...

Page 15: ...ommunicator circuit board allows the 411UD to be supplied by a power limited nonresettable 21 3 to 24 0 VDC UL tested range 15 10 This 24 VDC nominal operating power can be supplied by a UL listed 24 VDC power supply which in order to comply with UL 864 must be listed for Fire Protective Signaling Systems or by a nonresettable 24 VDC output from a control panel This nom inal 24 VDC power is then i...

Page 16: ...matically delay the trigger of their system trouble relays upon loss of AC If this is provided by the host panel use Channel 2 Be cer tain to verify the method employed by the host panel to be monitored The factory default programming for each channel is as follows Channel 1 fire alarm Channel 2 host control panel trouble Channel 3 fire supervisory Channel 4 AC Loss TB2 TB1 U8 U10 U11 J1 J2 J4 PH1...

Page 17: ...he relay is programmable for activation on fire alarm host panel trouble fire supervisory total communication failure AC loss and DACT trouble Relay Label Note that space is provided for labeling the function of the relay Write the function that has been programmed for the relay in the white box located below the relay designator FIGURE 2 3 Style B Channel Connections Normally Open Contact Device ...

Page 18: ...11UD be located as the first device on the incoming telephone circuit to properly function 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 RJ31X JACK RJ31X JACK J2 PH1 PH2 FIGURE 2 5 Wiring Phone Jacks To Premises Phone Green Wire Red Wire Red Wire Tip Ring Ring Tip Ring Tip Ring Tip To Premises Phone Primary Lines Incoming Telco Phone Lines Secondary Lines Incoming Telco Phone Lines Note Shorting bars inside RJ3...

Page 19: ...rammer 1 Remove all power from the 411UD 2 Remove the two screws holding the 411UD cover in place and remove the cover 3 Connect the Programmer cable to connector J2 located in the upper right corner of the 411UD Note that the key on the connector must align with the slot in the J2 connector 4 Reapply power to the 411UD 5 Operate the Programmer by pressing the MODE key Enter the appropriate four d...

Page 20: ...ited Wiring Requirements The four 411UD input channels are power limited circuits Power supplied to the 411UD must be power limited 12 or 24 volts filtered and nonresettable The two Relay circuits must be connected to power limited circuits Do not connect nonpower limited wiring to any circuits on the 411UD ...

Page 21: ...ral Station The 411UD digital communicator transmits system status reports to a central station via the public switched tele phone network Two supervised telephone line connections are made to interface the digital communicator to the telephone lines Both telephone lines are supervised by the 411UD for proper voltage The 411UD is capable of line seizure on both the primary and secondary telephone ...

Page 22: ... reenter the proper 4 digit code before pressing the ENTER STORE key Note that as information is entered into the 411UD the digits will scroll across the Programmer display from right to left ___6 __66 _667 6676 A pause of up to 10 seconds between each number is allowed while entering the code LAMP TEST KEY Pressing the Lamp Test key on the Programmer while the digital communicator is in Normal Mo...

Page 23: ...icating that the next digit can now be entered Press the 6 key on the keypad 6 will appear as the second digit on the display and the decimal point will move one position to the right Press the ENTER STORE to view the contents of address 86 DOWN ARROW Use the DOWN arrow key to decrement the memory address and view its content UP ARROW Use the UP arrow key to increment the memory address and view i...

Page 24: ...cimal point To program the first hour digit press the cor responding number on the Programmer keypad and then press the ENTER STORE key For example to program 2 00 PM 1400 in military time press 1 on the keypad and then the ENTER STORE key The number 1 will appear as the far left digit and the decimal point will move one position to the right indicating that the second digit from the left is now r...

Page 25: ...ode 7764 and pressing the ENTER STORE key 7764 spells PROG on a Touch Tone phone If an incorrect key is entered reenter the proper 4 digit code before pressing the ENTER STORE key Note that as information is entered into the 411UD the digits will scroll across the Programmer display from right to left ___7 __77 _776 7764 A pause of up to 10 seconds between each number is allowed while entering the...

Page 26: ... a 10 minute time out period Note that if the Programmer is in Trouble shoot Mode when the cable is removed the 411UD will revert to Normal Mode following a 20 minute time out period 3 3 1 DACT Programming Primary Central Station Phone Number 00 19 The first twenty addresses 00 19 are factory set to F 00_F to 19_F Programming is done as follows If your phone number is 484 7161 press 4 The display ...

Page 27: ...8 Table 3 3 All 3 1 4 1 and 4 2 Expanded Formats Primary on page 29 and Table 3 1 Ademco Contact ID Format Primary on page 28 Event Codes Setting Entries The Format selected in address 20 will cause the digital communicator to automatically program addresses 138 201 with the factory default settings Any of the Event Code settings may be altered Consult your Central Station prior to altering the ev...

Page 28: ...Channel 3 Fault Event Code 380 003 159 161 Primary Input Channel 4 Fault Event Code 380 004 162 164 Primary Phone Line 1 Voltage Fault Event Code 351 000 165 167 Primary Phone Line 2 Voltage Fault Event Code 352 000 168 170 Primary Phone Number 1 Comm Fault Event Code 354 001 171 173 Primary Phone Number 2 Comm Fault Event Code 354 002 174 176 Primary System Off Normal Fault Code 308 000 177 179 P...

Page 29: ...5 184 185 Primary Phone Number 1 Restoral Code AA 186 187 Primary Phone Number 2 Restoral Code AB 188 189 Primary System Off Normal Restoral Code AF 190 191 Primary System Test Message 99 192 193 Primary System Abnormal Test Message 91 194 195 Primary Upload Download Request Code 71 196 197 Primary Upload Successful Code 72 198 199 Primary Download Successful Code 73 200 201 Primary Upload Downloa...

Page 30: ... factory default entry of 0 If other test report times are needed enter 1 12 hour 2 8 hour or 3 6 hour Secondary Central Station Phone Number 30 49 Addresses 30 49 are factory set to F 30_F to 49_F Programming is typically done as follows If your phone number is 484 7161 press 4 The display will read 30_4 Press ENTER STORE to save the entry to memory and increment to the next address 31_F 152 Prim...

Page 31: ...nded 1800 Hz Carrier 2300 Hz ACK 8 4 1 Standard 1900 Hz Carrier 1400 Hz ACK 9 4 1 Expanded 1900 Hz Carrier 1400 Hz ACK A 4 2 Standard 1800 Hz Carrier 2300 Hz ACK B 4 2 Expanded 1800 Hz Carrier 2300 Hz ACK C 4 2 Standard 1900 Hz Carrier 1400 Hz ACK D 4 2 Expanded 1900 Hz Carrier 1400 Hz ACK E Contact ID DTMF 1400 2300 ACK F Future use The Format selected in address 50 will cause the digital communi...

Page 32: ...ondary Input Channel 3 Active Event Code 200 003 211 213 Secondary Input Channel 4 Active Event Code 301 004 214 216 Secondary Input Channel 1 Fault Event Code 380 001 217 219 Secondary Input Channel 2 Fault Event Code 380 002 220 222 Secondary Input Channel 3 Fault Event Code 380 003 223 225 Secondary Input Channel 4 Fault Event Code 380 004 226 228 Secondary Phone Line 1 Voltage Fault Event Code...

Page 33: ...A4 246 247 Secondary Phone Line 2 Restoral Code A5 248 249 Secondary Phone Number 1 Restoral Code AA 250 251 Secondary Phone Number 2 Restoral Code AB 252 253 Secondary System Off Normal Restoral Code AF 254 255 Secondary System Test Message 99 256 257 Secondary System Abnormal Test Message 91 258 259 Secondary Upload Download Request Code 71 260 261 Secondary Upload Successful Code 72 262 263 Sec...

Page 34: ...t of 0 9 or A F corresponding to the number of hours to be delayed in reporting the loss of AC power The factory default is 2 for 2 hour delay The valid entries are 0 no delay 1 1 hours 2 2 hours 3 6 hours 4 7 hours 5 8 hours 6 9 hours 7 10 hours 8 11 hours 9 12 hours A 13 hours B 14 hours C 15 hours D 16 hours E 17 hours F 18 hours Note Use when the host panel has a dedicated relay output Verify ...

Page 35: ... match the host panel relay output functions with the Input Channel functions Test all wiring connections completely All Input Channels require Normally Open contact closure to trigger Input Channels do not latch Input Channel 1 Function Selection 65 1 Factory default for Channel 1 is 0 for activation on Fire Alarm Enter 1 for Host Control Panel Trouble 2 for Fire Supervisory 4 for AC Loss Input C...

Page 36: ...annot be selected for inputs programmed for these fire applica tions Input Channel 4 Delay Timer 78 80 1 The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated Input Channel 4 Delay Timer is factory set to 000 seconds for no delay The timer may be programmed for a delay of from 0 to 179 seconds Inputs programmed for fire alarm host control panel...

Page 37: ...re Use 90 93 Service Terminal 1 Phone Number 94 113 Addresses 94 113 are reserved for the Service Terminal Number 1 phone number Factory default is all F s Valid entries are 0 9 plus A B C D and E Use F to designate the end of the phone number See Remote Site Upload Download on page 46 for additional information Ring Count on Primary Phone Line 114 115 Use this address to designate the number of r...

Page 38: ...r 4 digit code before pressing the ENTER STORE key Within five seconds repeat this entry by again pressing the MODE key followed by the 4 digit code 3337 and pressing the ENTER STORE key The display will read 3337 while the E2 nonvolatile memory storage area for all pro gramming options is being reprogrammed with the original default settings When reprogramming is complete the display will be blan...

Page 39: ...the same procedure used for the primary phone line A handset may be temporarily connected across transformer T1 of the 411UD as indicated in Figure 3 2 The handset when connected across T1 may be used only as an amplifier speaker or telephone with the keypad used for number dialing TB2 TB1 R41 U8 U10 U11 J2 PH1 PH2 J1 J4 FIGURE 3 2 Handset Speaker Connection Both Primary and Secondary Lines 411udb...

Page 40: ...ion will be reported to a central station over the remaining good phone line The digital communicator comes with line seizure capability provided for both the primary and secondary telephone line interfaces Any time that the DACT needs to make a call to a central station line seizure will disconnect any local premises phones sharing the same telephone line All transmissions to central stations wil...

Page 41: ... 5 7 9 Format 1 A C Format B D Report 3 1 4 1 Standard 4 1 Express 3 1 4 1 Expanded 4 2 Standard 4 2 Express 4 2 Expanded Fire Alarm SSS S FA SSS S FA FAFAFA FA 2 SSSS FAFA2 SSSS FAZ Fire Alarm Restore SSS S RFA SSS S RFA RFARFARFA RFA 2 SSSS RFARFA2 SSSS RFAZ Channel Input Trouble Channel Input Open SSS S TZ SSS S TZ TZTZTZ TZ Z SSSS TZTZ2 SSSS TZZ Channel Input Trouble Restore SSS S RTZ SSS S RT...

Page 42: ...e Supervisory Condition 2nd digit RV Fire Supervisory Condition Restore 1st digit RV2 Fire Supervisory Condition Restore 2nd digit X Test Report 1st digit X2 Test Report 2nd digit Y Trouble corresponding to the following 1 Not Used 2 Not Used 3 Not Used 4 Telco Primary Line Fault 5 Telco Secondary Line Fault 6 Not Used 7 Not Used 8 Not Used 9 Not Used A Communication Failure Primary Number B Commu...

Page 43: ...e Supervisory 3 System Troubles Host Panel Trouble active input programmed for trouble AC Fail after delay Channel Input faults Telephone line fault Communication trouble System Off Normal 4 Restoral Reports Fire Alarm Fire Supervisory Host Panel Trouble AC Channel Input fault Telephone line Communication System Off Normal 5 System Test 6 Upload Download events lowest priority Red LEDs are provide...

Page 44: ...e is printed out in the report as an E for New Event or R for New Restore 3 GG Group Number is fixed at 00 and cannot be changed 4 CCC Channel Input Number is transmitted as 001 for Channel Input 1 002 for Channel Input 2 003 for Channel Input 3 004 for Channel Input 4 Ademco Contact ID Reporting Structure A typical printout from a Central Station receiver such as the Ademco 685 of alarm and troub...

Page 45: ...ng service prior to installation The Compatibility Table provides a list of compatible receivers and associated software versions for the receivers Changes in the hard ware and or software by the receiver manufacturers may affect the receiver compatibility with the DACT After com pleting the installation communication between the DACT and Central Station Receiver must be tested and verified TABLE ...

Page 46: ... with the Service Terminal the communicator s green Modem LED and one of the red Phone Line active LEDs will remain on steady Upon termination of communication the green Modem LED will turn off and the red Phone Line active LED will turn off In order to contact the communicator the following must be true The digital communicator may be in any mode of operation including Normal Program Real Time Cl...

Page 47: ... terminates downloading processes the trouble or alarm locally and transmits the information to the Central Station s 5 1 1 Security Features Remote site upload and download with the 411UD have been carefully designed to include key security features to ensure proper functionality The key features are listed and explained below Secret Code Verification A secret code is stored in the communicator b...

Page 48: ...erminal If callback is requested perform steps 4 through 10 if no callback is requested perform steps 9 and 10 only 4 Identify the Service Terminal location 5 Hang up disconnect call 6 Call the Central Station s and transmit a request for upload download message if programmed to do so If this message is accepted the communicator will proceed to the next step 7 Return call to the Service Terminal 8...

Page 49: ...to the next step 7 Return call to the Service Terminal 8 Verify secret code 9 Begin downloading 10 Upon completion of download call the Central Station s back and report a successful download or failed upload download status if programmed to do so During the uploading process the fire protection remains active Should a system trouble or alarm condition occur the communicator immediately terminates...

Page 50: ...8 hours 6 for 9 hours 7 for 10 hours 8 for 11 hours 9 for 12 hours A for 13 hours B for 14 hours C for 15 hours D for 16 hours E for 17 hours F for 18 hours 61 Backup Reporting Enter 0 to report to Secondary phone number as backup only 1 to report to both Primary and Secondary phone number for all reports messages 2 reports go to first available receiver 62 Reserved for Future Use 63 Reserved for ...

Page 51: ...ilure 7 for DACT trouble 89 Trouble Call Limit Enter a 0 to disable this feature 1 to enable Trouble Call Limit Factory default is 0 for disabled 90 91 92 93 Future Use 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 Addresses 94 to 113 store the Service Terminal 1 Phone Number Valid entries are 0 9 and A E F designates the end of the phone number 114 115 Ring Count on Pr...

Page 52: ...t Time 0000 12 00 midnight 59 Secondary Number Test Time Interval 0 for 24 hours 60 AC Loss Reporting Delay 2 for 2 hour delay 61 Backup Reporting 0 to report to Secondary Central Station phone number as backup only 62 Future Use 63 Future Use 64 Communicator Enable Disable 0 disables communication to Central Station 65 Input Channel 1 Function Selection 0 for fire alarm 66 Input Channel 2 Functio...

Page 53: ...sses 94 to 113 store the Service Terminal 1 Phone Number Valid entries are 0 9 and A E F designates the end of the phone number 114 115 Ring Count on Primary Phone Line 03 for number of rings before answering call 116 Future Use 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 Addresses 117 to 137 store the Service Terminal 2 Phone Number Valid entries are 0 9 and A ...

Page 54: ...46 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 B 2 4 2 Standard 4 2 Express Formats Secondary Central Station 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 23...

Page 55: ...186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 B 4 4 2 Standard 4 2 Express Formats Secondary Central Station 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 1 1 F F 8 3 9 2 F...

Page 56: ...206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 B 7 All 3 1 All 4 1 and 4 2 Expanded Formats for Primary Central Station Factory Defaults 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 B 8 All 3 1 All 4 1 and 4 2 Expanded Formats for Secondary Central Sta...

Page 57: ... 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 B 11 Ademco Contact ID Format Primary Central Station Factory Defaults 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 B 12 Ademco Contact ID Format Secondary ...

Page 58: ...18 Near Alarm FIRE Near Alarm Panic Alarms 120 120 Panic Alarm PANIC Panic 121 Duress PANIC Duress 122 Silent PANIC Silent Panic 123 Audible PANIC Audible Panic Burglar Alarms 130 130 Burglary BURG Burglary 131 Perimeter BURG Perimeter 132 Interior BURG Interior 133 24 Hour BURG 24 Hour 134 Entry Exit BURG Entry Exit 135 Day Night BURG Day Night 136 Outdoor BURG Outdoor 137 Tamper BURG Tamper 138 ...

Page 59: ...ow Water Pressure 202 Lox CO2 SUPER Low CO2 203 Gate valve sensor SUPER Gate Valve 204 Low water level SUPER Low Water Level 205 Pump activated SUPER Pump Activation 206 Pump failure SUPER Pump Failure System Troubles 300 and 310 300 System trouble TROUBLE System Trouble 301 AC loss TROUBLE AC Power 302 Low system battery TROUBLE System Low Battery 303 RAM checksum bad TROUBLE Bad RAM Checksum Res...

Page 60: ...rouble TROUBLE Sensor Trouble 381 Loss of supervision RF TROUBLE RF Sensor Supervision 382 Loss of supervision RPM TROUBLE RPM Sensor Supervision 383 Sensor tamper TROUBLE Sensor Tamper 384 RF transmitter low battery TROUBLE RF Sensor Batt Open Close 400 400 Open Close OPENINGCLOSING 401 Open Close by user OPENING User CLOSING User 402 Group Open Close OPENING Group User CLOSING Group User 403 Aut...

Page 61: ...sabled DISABLE Dialer Disable 552 Radio transmitter disabled DISABLE Radio Disable Bypasses 570 570 Zone bypass BYPASS Zone Bypass 571 Fire bypass BYPASS Fire Bypass 572 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 Manual trigger test TEST Manually TriggeredRestore not applicable 602 Periodic test report TEST...

Page 62: ...AGE Channels Inputs Connects to normally open contact trig gers DACT Untwisted unshielded wire Do not exceed 100 ohms 10 000 3 000m 8 000 2 400m 4 875 1 450m 3 225 980m 12 AWG 3 25 mm2 Signal 88202 Belden 9583 WPW999 14 AWG 2 00 mm2 Signal 88402 Belden 9581 WPW995 16 AWG 1 30 mm2 Signal 88602 Belden 9575 WPW991 18 AWG 0 75 mm2 Signal 88802 Belden 9574 WPW975 Output Relay must connect to power limi...

Page 63: ...n 2525 CLCK Enters Real Time Clock Mode Program digital communicator time Fire protection is off 7764 PROG Enters Program Mode Allows programming of digital communicator Fire protection is off 3337 DEFP Returns digital communicator to factory default program settings Fire protection is off during Default Mode 8768 TROU Allows testing of both telephone lines Fire protection is off during Troublesho...

Page 64: ...irections 3 The 411UD DACT relay must be enabled refer to Output Relay Enable 87 on page 36 and must be programmed to activate on DACT trouble refer to Output Relay Function Selections 88 on page 37 4 The Auxiliary Trouble Input wiring from the 411UD DACT must be in conduit and in the same room as the FACP and DACT J4 under cover jumper not installed jumper VDC to relay terminal 24 VDC nonresettab...

Page 65: ...nel Installation 18 J Jumper J4 9 12 VDC 9 15 24 VDC 9 15 L LED see Indicator Line Seizure 12 M Modes of Operation 14 21 63 Mounting 8 15 N Normal Mode 14 21 O Off On Hook 12 P Phone 10 Circuit 12 18 Line Testing 38 Piezo see also Sounder 9 PK 411 46 see also Upload Download 9 Power 9 10 Operating 12 VDC 9 15 24 VDC 9 15 Current Requirements 9 UL Tested Range 9 PRO 411 see Programmer Program Mode ...

Page 66: ...66 411UD Document 50759 Rev E 12 09 2008 P N 50759 E Notes ...

Page 67: ...n Material Authorization form from our Return Authorization Department This writing constitutes the only warranty made by Honeywell International Inc with respect to its products Honeywell International Inc does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer ackn...

Page 68: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...

Reviews: