Input Channels
16
411UD Document #50759 Rev. E 12/09/2008 P/N 50759:E
Each input channel monitors a normally open device and may be programmed as follows:
• fire alarm
• host control panel trouble
• fire supervisory
• AC Loss
Programming the input channel automatically programs the transmitted event code, however, the event code can be
changed since it is fully programmable. Event code transmissions can be tailored to the specific application and
requirements of the Central Station.
AC Loss Reporting: Channel 4, which is defaulted to AC Loss, will transmit a specific AC loss signal only if the
assigned Normally Open contact provides this function. Some panels provide an option that will automatically delay
the trigger of their system trouble relays upon loss of AC. If this is provided by the host panel, use Channel 2. Be cer-
tain to verify the method employed by the host panel to be monitored.
The factory default programming for each channel is as follows:
Channel 1 - fire alarm
Channel 2 - host control panel trouble
Channel 3 - fire supervisory
Channel 4 - AC Loss
TB2
TB1
U8
U10
U11
J1
J2
J4
PH1
R41
PH2
M300
FIGURE 2-2:
Typical FACP Connection to 411UD
Addressable FACP
411UD
24 VDC nonresettable power
+ -
Supervisory
Relay
Trouble
Relay
Alarm Relay
Channel 1
Channel 2
Channel 3
Channel 4
2.2K EOLS
P/N 27070
47K EOL
SLC Loop
J4 Not Installed
Relay Output
(DACT Trouble)
Monitor Module
Circuit Input
Note: The monitor module input,
which is being used to monitor the
411UD Relay Output (programmed
for DACT Trouble), must be pro-
grammed as 'DACT Trouble' at the
FACP
2.2K
EOL