411UD Document #50759 Rev. E 12/09/2008 P/N 50759:E
45
Central Station Communications
The following table contains UL listed receivers compatible with the 411UD digital communicator.
(1) With version 3.9 software.
(2) With 685-8 Line Card with Rev. 4.4d software.
(3) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software.
(4) With 124077V2.00 Receiver and 126047 Line Card Rev. M.
(5) With V.7301 Receiver S/W.
(6) With 01.01.03 Receiver S/W and Line Card 01.01.03.
(7) Surgard System III software version 1.6.
(8) Surgard MLR-2 software version 1.86.
(9) With DSP4016 and V1.6 Line Card.
(10) With 124060V206B and 124063 Line Card Rev. B
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/Transmitter is com-
patible with the Central Station Receiver, utilized by the monitoring service, prior to installation. The Compatibility
Table provides a list of compatible receivers and associated software versions for the receivers. Changes in the hard-
ware and/or software by the receiver manufacturers may affect the receiver compatibility with the DACT. After com-
pleting the installation, communication between the DACT and Central Station Receiver must be tested and verified.
TABLE 4-3:
Compatible UL Listed Receivers
Format #
(Addresses 20 and 50)
FB
I
C
P
2
20F
B (1
)
Ad
emco
6
85 (2)
Si
le
nt Kni
ght
9000
(3
)
Si
le
nt Kni
ght
9800
(4
)
Osbo
rn
e Hoffman
2000
E (5
)
Ra
di
on
ic
s
6600
(6
)
Surgard
System II
I (
7
)
Surgua
rd
MLR-2 (8)
Surgua
rd
MR-2000 (9)
Ad
emco
MX8
000 (10
)
0
4+1 Ademco Express
1
4+2 Ademco Express
2
3+1/Standard/1800/2300
3
3+1/Expanded/1800/2300
4
3+1/Standard/1900/1400
5
3+1/Expanded/1900/1400
6
4+1/Standard/1800/2300
7
4+1/Expanded/1800/2300
8
4+1/Standard/1900/1400
9
4+1/Expanded/1900/1400
A
4+2/Standard/1800/2300
B
4+2/Expanded/1800/2300
C
4+2/Standard/1900/1400
D
4+2/Expanded/1900/1400
E
Ademco Contact ID