Input Channels
FIGURE 2-7:
Typical Addressable FACP Connection to 411UDAC
411UDAC
Note: The addressable monitor module
input, which is being used to monitor the
411UDAC Relay Output programmed for
DACT Trouble (requires optional 411RK
Relay Kit), must be programmed as
'DACT Trouble' at the FACP. The
411UDAC must be programmed as a
Slave Communicator (programming
address 64 set to ‘2’)
Addressable FACP
(must be UL-listed for
Central Station Service
and Remote Signaling
Service)
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Channel 1/Zone 1
Channel 3/Zone 3
2.2K EOL Channel 4
2.2K
EOL
Monitor Circuit Input
SLC Loop
Trouble Relay
Alarm Relay
Supervisory Relay
UL listed
2.2K EOLs
P/N 27070
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
920
041
1A
.CDR
Monitor
Module*
End-of-Line Resistor
supplied with
Monitor Module
*If the SLC device does not
match the one in this figure,
refer to the SLC manual wiring
conversion charts for legacy
and newer versions of the
modules.