Programming Sheets
68
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
75
76
77
Input Channel 3 Delay Timer. Enter 0 - 179 seconds delay.
Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
78
79
80
Input Channel 4 Delay Timer. Enter 0 - 179 seconds delay.
Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
81
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
82
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
83
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
84
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
85
Output Relay #1 enable. Enter '1' to enable Relay #1; '0' to disable relay.
86
Output Relay #1 Function. Enter '0' for relay to activate on alarm; '1' host panel trouble; '2' DACT trouble; '3'
for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' for total communication failure.
87
Output Relay #2 enable. Enter '1' to enable Relay #2; '0' to disable relay.
88
Output Relay #2 Function. Enter '0' for relay to activate on fire alarm; '1' host panel trouble; '2' for DACT
trouble; '3' for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' total communication
failure.
89
Reserved for future use. Leave default setting of ‘0.’
90
Reserved for future use. Leave default setting of ‘0.’
91
Alarm verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
92
Silence inhibit. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC for one minute.
93
Autosilence. Enter '0' for no autosilence; '1' for 5 minute autosilence; '2' for 10 minutes; '3' for 15 minutes; '4'
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
94
Restoral method. Enter '0' for Typical restoral method; '1' for Conditional Restoral Method #1; '2' for
Conditional Restoral Method #2.
95
Coding, Notification Appliance Circuit. Enter ‘0’ for no coding (steady); ‘1’ for Temporal coding.
96
Trouble Call Limit - Dialer Runaway Prevention Feature. Enter a '0' to disable this feature; '1' to enable Trou-
ble Call Limit. Factory default is '0' for disabled.
97
98
99
100
Panel Identification Number.
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
Addresses 101 to 120 store the Service Terminal 1 Phone Number.
Valid entries are 0 - 9 and
A - E. 'F' designates the end of the phone number.
121
122
Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call.
Valid entries
are 00 to 25 (00 = no answer). Factory default is 03.
123
FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
Addresses 124 to 143 store the Service Terminal 2 Phone Number.
Valid entries are 0-9 and A-E.
'F' designates the end of the phone number.
144
Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary Central
Station Phone Number on backup only; '1' for Upload/Download reports to always go to the Secondary; '2' for
Upload/Download reports to go to the first available Central Station phone number.
Summary of Contents for FIRE-LITE 411UDAC
Page 4: ...4 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...
Page 84: ...84 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...
Page 85: ...411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D 85 Notes ...
Page 86: ...86 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...